Chapter 6 Web Page Of MSC-C 79
SmartCabinet Integrated Solution User Manual
Figure 6-51 Monitoring unit (Sampling)
As for the operation method of the three tabs of
Sampling
,
Setting
and
Alarm
on the Monitoring unit page, refer to
6.4.1 Cabinet Data
.
Note
On the
Setting
tab, if you set
‘
Blocked
’
for
Outgoing Alarm Blocked
, when an alarm occurs, it will be blocked, in this case:
1. For current alarms, the page only displays the alarm signals, but not send alarm notifications; after the alarm disappears, it will
not be saved in history alarm;
2. The
‘
Blocked
’
setting for
Outgoing Alarm Blocked
will be automatically cleared in 24h.
Network Setting
1. IP Setting
Click the
Network Setting
submenu under the
System Options
menu, the page shown in Figure 6-52 pops up.
Figure 6-52 IP setting
On the page shown in Figure 6-52, you can configure the network parameters, such as IP addressing mode,
IP
,
Mask
,
Default Gateway
,
DNS1
(Preferred DNS server) and
DNS2
(Alternate DNS server). After modifying the
network parameters, click the
Save
button to make the setting effective.
Note
After modifying the IP address, the system will jump to the new IP address by default. You must use the new IP address to
re-login the MSC-C.
2. Access Management
Click the
Network Setting
submenu under the
System Options
menu, and then click the
Access Management
tab,
the page shown in Figure 6-53 pops up.