48
SI-DeviceNet User Guide
Issue Number: 2
6
Pr
10.007
Above set speed
Only set if the drive is running at above set speed. Refer to
Pr
03.006
, Pr
03.007
and Pr
03.009
in the drive documentation for
more details.
7
Pr
10.008
Load reached
Indicates that the modulus of the active current is greater or equal
to the rated active current, as defined in menu 4. Refer to the drive
documentation for more details.
8
Pr
10.009
In current limit
Indicates that the current limits are active.
9
Pr
10.010
Regenerating
Indicates that power is being transferred from the motor to the
drive.
Regen mode: Indicates that power is being transferred from the
drive to the supply.
10
Pr
10.011
Dynamic brake active
Indicates that the braking IGBT is active. If the IGBT becomes
active, this parameter will remain on for at least one second.
11
Pr
10.012
Dynamic brake alarm
Dynamic brake alarm is set when the braking IGBT is active, and
the braking energy accumulator is greater than 75 %.
12
Pr
10.013
Reverse direction commanded
Direction commanded is set to 1 if the Pre-ramp speed reference
(Pr
01.003
) is negative and reset to 0 if the Pre-ramp speed
reference is zero or positive.
13
Pr
10.014
Reverse direction running
A 0 indicates forward direction and a 1 indicates reverse direction.
The source of this bit is Pr
02.001
for open loop mode and
Pr
03.002
for RFC-A and RFC-S modes.
14
Pr
10.015
Supply loss
Supply loss indicates that the drive has detected a supply loss from
the level of the DC bus voltage. This parameter can only become
active if supply loss ride through or supply loss stop modes are
selected.
In regen mode, supply loss is the inverse of Pr
03.007
.
15
(Not Used)
Reserved
Bit
Parameter
Description