Issue Number: 2
All possible values of
S.01.006
are given in the table below.
The network loss detection feature provides a method which ensures that
communication with the master is still present. The SI-DeviceNet resets an internal
timer when a valid message is received from the DeviceNet network, if a message is not
received within the specified period, network loss is detected.
Network loss detection is not enabled internally until cyclic data has been detected. This
prevents spurious network loss timeouts while the DeviceNet master controller is
initializing the DeviceNet network.
Pr
S.01.011
determines the action to take when a timeout specified by Pr
S.01.010
occurs. All possible actions and descriptions are listed below.
Value
Text
Description
0
Network OK
Network ok/healthy
1
Init OK
The SI-DeviceNet has initialized correctly and is waiting
for the DeviceNet master to initialize communications.
2
No Cyclic
No cyclic data has been recognized. This could be due to
the length of the mapping data is not equal to the master
setup.
3
Init Failed
A part of the SI-DeviceNet initialization sequence was not
successful. If this fault persists after a power-cycle,
replace the SI-DeviceNet.
4
Comm Fault
Fault found in the communications of the module. This
could be due to different devices configured to use
different baud rates.
5
No 24 V
No 24 V external PSU has been detected.
6
Baud detecting Automatic baud rate detection is in progress.
7
Initializing
The module is currently initializing.
Network loss selection
S.01.010
Default
200 ms
Range
0 to 3000 ms
Access
RO
Timeout action
S.01.011
Default
Trip (0)
Range
Trip (0) to No action (4)
Access
RW
Value
Text
Description
0
Trip
Trip the drive
1
Send flt values
Send fault values to output parameters
2
Clear output
PLC output parameters will have values set to zero
3
Hold last
Hold the last value in the PLC output parameters
4
No action
No action with output parameters