User Instructions
Part Number IOM – 87376-7 July 2016, Rev 1.0
54
Table 17.
Step Mode Table
Menu
Item
Sub Menu
Item
Poss. Setting
Notes/Comments
P12.1
Step Mode
Function
Mode
Disabled
Step mode operation is disabled
Enabled
Step mode operation is enabled in LOCAL,
REMOTE and EMERGENCY operation.
Local only
Step mode mode is only enabled in LOCAL mode
Remote only Step mode mode is only enabled in REMOTE mode
Local +
Remote
only
Step mode is enabled in REMOTE and
LOCAL mode
P12.2
Step Mode
Function
Start Open
0 - 100%
In OPEN direction, position in % from which the
step mode operation should start.
P12.3
Step mode
Function
End Open
0 - 100%
In OPEN direction, position in % of which the step
mode operation should end.
P12.4
Step Mode
Function
Runtime
Open
0.1 - 60
Runtime in OPEN direction
P12.5
Step Mode
Function
Pause Time
Open
0.2 - 60
Pause time in OPEN direction
P12.6
Step Mode
Function
Start Closed
0 - 100%
In CLOSED direction, position in % from which the
step mode operation should start.
P12.7
Step Mode
Function
End Closed
0 - 100%
In CLOSED direction, position in % of which the
step mode operation should end.
P12.8
Step Mode
Function
Runtime
Closed
0.1 - 60
Runtime in Closed direction
P12.9
Step Mode
Function
Pause Time
0.2 - 60
Pause time in Closed direction
P12.10 Step Mode
Function
Timebase
0: Seconds
Time basis for run and pause times
1: Minutes
Figure 59
Step Mode Operation
NOTE:
It is important to ensure that the mode of operation is not exceeded. The running info on the
actuator (see
Section 17.2.2
) only flashes while the drive is running, i.e., during the break, no
flash.
Содержание RTS FQ
Страница 2: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 0 ii ...
Страница 6: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 0 iv ...
Страница 7: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 v ...
Страница 89: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 0 82 ...