User Instructions
Part Number IOM – 87376-7 July 2016, Rev 1.0
42
CAUTION: OBSERVE PROPER POSITIONING
Generally, 100% stands for fully open and 0% for fully closed. Please note that these values
cannot be changed.
Table 7.
End Limit Table
Menu Item
Sub Menu
Item
Poss. Setting
Notes /Comments
P1.1
End limit
Open
TEACHIN;
0-100U1)
The parameter value can be set using TEACHIN.
With a known travel, the second end position can be
entered after setting the first end position.
P1.2
End limit
Close
TEACHIN;
0-100U1)
The parameter value can be set using TEACHIN.
With a known travel, the second end position can be
entered after setting the first end position.
P1.3
End limit
Switch off
Open
by travel (0)
The actuator uses end position signals to switch off and
report the end position.
by torque (1)
The actuator signals the end position or stops the motor
only after reaching the specified torque with the proviso
that it has reached the end position. If the end position
signal is not reached, the actuator reports an error.
P1.4
End limit
Switch off
Close
by travel (0)
The actuator uses end position signals to switch off and
report the end position.
by torque (1)
The actuator signals the end position or stops the motor
only after reaching the specified torque with the proviso
that it has reached the end position. If the end position
signal is not reached, the actuator reports an error.
P1.5
End limit
Closing
directing
right (0)
Actuator is designed for clockwise = closing
left (1)
Reverse direction of rotation. Counterclockwise = closing.
The crossing of all signals and commands is performed by
the controller.
P1.6
End limit
Rotate sense
position
0
No function at RTS FQ Fail-Safe Quarter-Turn Series.
1
P1.7
End limit
LED function
Close = green (0) Definition of the LED colour of the CLOSED or OPEN end
position signalization.
Close = red (1)
P1.8
End limit
End limit
hysteresis
0,1 - 10,0%
Hysteresis range for end position signals, Example:
End position hysteresis 1% means, that the end position
OFF is reached when closing 0%, and will leave it when
opening only at 1%, i.e., a reclosing can only take place
after leaving this hysteresis.
CAUTION: OBSERVE LIMITS AND FACTORS OF GEAR
When installing the actuator on an gear or a thrust unit, please take into account the limits and
factors of the gear/thrust unit at parameterization.
When using end limit switch off by torque, the end position limit must be set before reaching
the torque limit. Accordingly, the actuator will only signal the final end position if the
configured torque and the associated end position are reached. If the end position is not
reached, a torque error is reported (see
Section 17.2.2
).
Содержание RTS FQ