28
RSTi-EP CPE200 Series Controllers Quick Start Guide
GFK-3109B
EPXCPE205 Network Configuration
Procedure
The EPXCPE205 supports two network operating modes: Single LAN
and Dual LAN operating modes. To switch between the modes, the
user must use the Set Operating Mode menu, which is accessible
from the controller web page. (See steps below.)
IMPORTANT: Changing the operating modes will clear all user-
stored controller logic. The IP addresses, controller, and IO
faults will remain.
1.
Begin by navigating to the controller web page by entering the
IP address of the LAN you are connected to into the web
browser.
2.
At the top-right of the page, select the Operating Mode tab and
select
Change Operating Mode
.
3.
Once redirected to the change operating mode page, select the
operating mode you wish to configure.
Note
: if the user selects
the operating mode that they are currently in, nothing will
happen.
4.
To confirm the selection, press and hold the physical presence
button on the controller until the webpage says to release it.
5.
The controller will now reboot and come up in the new
operating mode.
Содержание RSTi-EP CPE200 Series
Страница 2: ...RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Dec 2022 ...
Страница 15: ...12 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 3 Power Feed Minimum Current Draw ...
Страница 16: ...13 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 4 Power Feed Maximum Current Draw ...
Страница 28: ...25 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 6 Single LAN Mode ...
Страница 29: ...26 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 7 Dual LAN Mode ...