41
8.2.2 RTD for Sensor 1 is Open or Shorted.
There is an open or short in the sensor RTD or wiring.
A. If sensor is being installed for the first time, check the wiring connections. See Section 3.2.
B. Disconnect the sensor from the analyzer and measure the resistance between the RTD lead wires. See the
sensor manual to identify the RTD leads. If there is an open or short circuit, replace the sensor.
C. If there is no open or short, check the analyzer. See Section 8.5.
MODEL SOLU COMP II
SECTION 8.0
TROUBLESHOOTING
SECTION 8.0
TROUBLESHOOTING
8.1 OVERVIEW
8.2 TROUBLESHOOTING USING FAULT CODES
8.3 TROUBLESHOOTING WHEN NO ERROR MESSAGE IS SHOWING — OZONE
8.4 TROUBLESHOOTING WHEN NO ERROR MESSAGE IS SHOWING — GENERAL
8.5 SIMULATING INPUTS
8.6 SIMULATING TEMPERATURE
8.1 OVERVIEW
The Solu Comp II continuously monitors itself and the sensor for faults. When the analyzer detects a fault, the
word
fault
appears in the display alternately with the measurement. If alarm 3 was configured as a fault alarm,
the alarm relay will energize. The outputs do not change during a fault condition. They continue to reflect the
measured ozone or temperature.
Press
"
to display the fault codes.
NOTE
A large number of information screens are available to aid troubleshooting. The most useful of these are
raw sensor current and sensitivity and zero current at last calibration. To view the information screens,
go to the main display and press the
'
key.
8.2 TROUBLESHOOTING USING FAULT CODES
8.2.1 Sensor Current Exceeds 210
µµ
A
Excessive sensor current implies that the sensor is miswired or the sensor has failed.
Fault Code
Explanation
See Section
S1 Out of Range
Sensor current exceeds 210
µ
A
8.2.1
TC1 Open
RTD for sensor 1 (ozone) is open
8.2.2
TC1 Shorted
RTD for sensor 1 (ozone) is shorted
8.2.2
S1 Sense Line Open
RTD sense line for sensor 1 (ozone) is open
8.2.3
EEPROM Failure
EEPROM failure
8.2.4