Common Magmeter Issue
(continued)
Table 12-7:
Symptom
Potential cause
Corrective action
Electronics failure
Verify transmitter operation with an 8714D Calibra-
tion Standard or replace the electronic stack
Blown fuse
Check the fuse and replace with an appropriately
rated fuse, if necessary
Output at 4 mA
Transmitter in multidrop mode
Configure Poll Address to 0 to take transmitter out
of multidrop mode
Low Flow Cutoff set too high
Configure Low Flow Cutoff to a lower setting or in-
crease flow to a value above the low flow cutoff
PZR Activated
Open PZR switch at terminals 5 and 6 to deactivate
the PZR
Flow is in reverse direction
Enable Reverse Flow function
Shorted coil
Coil check – perform sensor test
Empty pipe
Fill pipe
Electronics failure
Verify transmitter operation with an 8714D Calibra-
tion Standard or replace the electronics stack
Output will not reach 20
mA
Loop resistance is greater than 600
ohms
Reduce loop resistance to less than 600 ohms
Perform analog loop test
Insufficient supply voltage to analog
output
Verify analog output supply voltage
Perform analog loop test
Output at 20.8 mA
Transmitter not ranged properly
Reset the transmitter range values – see
Check tube size setting in transmitter and make
sure it matches the actual tube size – see
Output at alarm level
Electronics failure
Cycle power. If alarm is still present, verify transmit-
ter operation with an 8714 D Calibration Standard
or replace the electronics stack
Open coil circuit
Check coil drive circuit connections at the sensor
and at the transmitter
Analog output diagnostic alarm is ac-
tive
See
Coil power or coil current is over limit
Check coil drive circuit connections at the sensor
and at the transmitter
Cycle power. If alarm is still present, verify transmit-
ter operation with an 8714 D Calibration Standard
or replace the electronics stack
Connected to incompatible sensor
See
Pulse output at zero, re-
gardless of flow
Wiring error
Check pulse output wiring at terminals 3 and 4. Re-
fer to wiring diagram for pulse counter and pulse
output. See
PZR activated
Remove signal at terminals 5 and 6 to deactivate
the PZR.
Troubleshooting
Reference manual
167
Содержание Rosemount 8732EM
Страница 2: ......
Страница 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 87: ...Field Communicator Dashboard Menu Tree HART v5 4 part 2 Figure 7 8 Operation Reference manual 81 ...
Страница 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 138: ...Advanced Diagnostics Configuration 132 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Страница 221: ...Wiring Diagram 475 Field Communicator with 8732EM External Analog Power Figure C 6 Wiring Diagrams Reference manual 215 ...
Страница 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Страница 253: ...Implementing a Universal Transmitter Reference manual 247 ...