5. Change the operating mode to
Run App
.
6. Press the
Esc
button repeatedly until the
Full PV display
appears.
In the bottom-right of the display is now the word
LOG
, flashing to indicate that
data logging is operating.
Related information
4.4.12
Set-up the current output
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
CURRENT OUTPUT
The current output is for transmitting the control unit PV value (D800) as a 4–20 mA
signal. The output is calculated by using the range values of parameters P400 and P401.
Consider a control unit PV value of 5 meters and the PV range is 0 to 10 meters:
•
0 meters is represented by a 4 mA signal (0%)
•
5 meters is represented by a 12 mA signal (50%)
•
10 meters is represented by 20 mA signal (100%)
Therefore, the Current Output would output the PV value five meters as a 12 mA signal.
Note
The current output is frozen while the control unit is in the program operating mode.
Reference Manual
Getting started
00809-0100-4841
January 2021
Emerson.com/Rosemount
91
Содержание Rosemount 3490 Series
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Страница 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Страница 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Страница 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Страница 158: ...Specifications and reference data Reference Manual January 2021 00809 0100 4841 158 Emerson com Rosemount ...
Страница 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Страница 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...