c. The Intrinsically Safe outputs of the control unit may be connected to
certified equipment used in a hazardous area requiring Equipment Protection
Level Ga or Da (category 1) equipment, with flammable gas and vapor
groups IIC, IIB and IIA, and flammable dust groups IIIC, IIIB, and IIIA. No
additional I.S. barrier is required.
d. If the circuit connected to terminals 1 and 2 does not satisfy IEC60079-11
(EN60079-11) clause 6.3.13 (Isolation of circuits from earth or frame), then
equipotential earthing/grounding to the control unit intrinsically safe earth/
ground shall be provided.
An example of equipotential earthing/grounding is a cable with a cross-
sectional area greater than 4 mm
2
and a resistance of less than 1 Ohm.
4. Technical data:
a. Coding:
ATEX
II (1) GD
[Ex ia] IIC (–40 °C ≤ Ta ≤ 55 °C)
[Ex ia Da] IIIC (–40 °C ≤ Ta ≤ 55 °C)
IECEx
[Ex ia] IIC (–40 °C ≤ Ta ≤ 55 °C)
[Ex ia Da] IIIC (–40 °C ≤ Ta ≤ 55 °C)
b. Safety parameters:
Terminals T1 (24 V) with respect to T2
(I
in
) and T1 (24 V) with respect to T3
(Earth)
Terminals T2 (I
in
) with respect to T3
(Earth)
Ui = 0, Uo = 27.3 V, lo = 96.9 mA, Po =
0.66 W, Li = 0.22 mH, Ci = 0.6 nF
Ui = 30 V, li = 120 mA, Li = 0.1 mH, Ci =
0.6 nF, Uo = 6.51 V (capacitive charging
only), Io = 0, Po = 0
(1)
Terminal T2 (I
in
) with respect to terminal T3 (Earth) must be treated as a 6.51 V
source. The 6.51V is considered as being theoretical maximum to which a
capacitive load across these terminals could become charged through leakage
via internal series blocking diodes. This voltage does not contribute to the short
circuit sparking risk of any external source connected to these terminals.
c. The
capacitance
and
inductance
of the load connected must not exceed the
following values:
Group
Capacitance
Inductance (mH) or L/R Ratio (μH/
Ohm)
IIC
1.2 mH
42 μH/Ohm
IIB
0.65 μF
10.9 mH
172 μH/Ohm
IIA
2.15 μF
21.9 mH
346 μH/Ohm
(1)
0.082 μF of which total Ci of the hazardous area apparatus connected must not
exceed 0.020 μF.
Product certifications
Reference Manual
January 2021
00809-0100-4841
162
Emerson.com/Rosemount
Содержание Rosemount 3490 Series
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Страница 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Страница 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Страница 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Страница 158: ...Specifications and reference data Reference Manual January 2021 00809 0100 4841 158 Emerson com Rosemount ...
Страница 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Страница 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...