![Emerson Rosemount 3490 Series Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/emerson/rosemount-3490-series/rosemount-3490-series_reference-manual_2400788058.webp)
Using the App Wizard to set-up a flow application
Inputs:
•
Level measurement in feet from transmitter.
•
Open channel is a 60° V-Notch Weir.
•
Maximum flow is 645.50 gallons per minute.
•
Height at maximum flow is 1 ft.
Outputs:
•
Flow rate in gallons per minute.
•
Totalized flow in gallons x 100.
•
2% low flow cut-off.
Getting started
Reference Manual
January 2021
00809-0100-4841
58
Emerson.com/Rosemount
Содержание Rosemount 3490 Series
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Страница 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Страница 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Страница 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Страница 158: ...Specifications and reference data Reference Manual January 2021 00809 0100 4841 158 Emerson com Rosemount ...
Страница 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Страница 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...