![Emerson Rosemount 3490 Series Скачать руководство пользователя страница 109](http://html.mh-extra.com/html/emerson/rosemount-3490-series/rosemount-3490-series_reference-manual_2400788109.webp)
Note
If Pump 1 keeps the level below 8 m, it would stay switched on until the level is 2 m.
Related information
Totalizer mode relay
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
TOTALIZER
A Totalizer relay can output a pulse for each time that the internal totalizer count (D828)
increments. The duration of the pulse may set using parameter P534.
Note
If the totalizer count is running faster than the relay can produce pulses, an internal
accumulator stores the excess pulses. The stored excess pulses are output by the Totalizer
relay after the totalizer count rate reduces.
Table 4-12: Totalizer Mode Relay Parameter
Parameter
Description
Factory default
P534
Pulse Width
The duration controls both the 'On' time and the 'Off'
time - i.e. the pulse width - and may be set to a value
between 10 ms and 2.5 seconds in steps of 10 ms.
100
Sampler mode relay
Menu
SETUP
→
[CONTROLLER]
→
OUTPUT
→
TOTALIZER
Sampler relays output pulses at a slower rate than a Totalizer relay. The Sampler relay can
be used as a coarse totalizer or as a trigger to an external event.
Table 4-13: Sampler Mode Relay Parameter
Parameter
Description
Factory default
P535
Sampler Factor
This is for defining the frequency of the Sampler
pulse. For example, a value of 100 means that the
Sampler relay outputs a single pulse for every 100
th
increment to the Totalizer Count (D828/D829)
The pulse width is the same as selected for the
Totalizer relay (P534)
0
Related information
Reference Manual
Getting started
00809-0100-4841
January 2021
Emerson.com/Rosemount
109
Содержание Rosemount 3490 Series
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Страница 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Страница 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Страница 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Страница 158: ...Specifications and reference data Reference Manual January 2021 00809 0100 4841 158 Emerson com Rosemount ...
Страница 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Страница 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...