50
Reference Manual
00809-0100-4107, Rev BA
Section 3: Hardware Installation
April 2013
Drain/
Vent
Valve
Drain/
Vent Valve
Equalize
(open)
Process
Isolate
(closed)
Isolate
(open)
H
L
2.
Open the center (equalize)
valve to equalize the pressure
on both sides of the
transmitter. The manifold
valves are now in the proper
configuration for zeroing the
transmitter.
Drain/
Vent
Valve
Drain/
Vent Valve
Equalize
(closed)
Process
Isolate
(closed)
Isolate
(open)
H
L
3.
After zeroing the transmitter,
close the equalizing valve.
Drain/
Vent
Valve
Drain/
Vent Valve
Equalize
(closed)
Process
Isolate
(open)
Isolate
(open)
H
L
4.
Open the block valve on the
low pressure side of the
transmitter to return the
transmitter to service.