ROC800-Series Instruction Manual
3-24
Power Connections
Revised July-2017
Table 3-19. Power Consumption of the HART-2 Module
Other Device
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
HART-2 Module Base
110 mA @ 12 volts dc
1320 mW
Each Channel
Channel’s mA current
draw from +T * 2.50 * 12
Table Total
Table 3-20. Power Consumption of the IEC 62591 Module
I/O Module
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
IEC 62591 Module
1
Pm-12 (12V) WiHart card
only
552 mW
1
Pm-24 (24V) WiHart card
only
720 mW
1
PM-30 (12V) WiHart card
only
696 mW
1
PM-30 (24V) WiHart card
only
792 mW
1
PM-30 (30V) WiHart card
only
930 mW
1
Pm-12 (12V) WiHart w/
Transmitter
1080 mW
1
Pm-24 (24V) WiHart w/
Transmitter
1200 mW
1
PM-30 (12V) WiHart w/
Transmitter
1116 mW
1
PM-30 (24V) WiHart w/
Transmitter
1392 mW
1
PM-30 (30V) WiHart w/
Transmitter
1500 mW
1
Table Total
Duty Cycle
An IEC 62591 has
no
associated duty cycle. Consequently, always set
“1” as the duty cycle value.
Table 3-21. Power Consumption of the NRM Module
I/O Module
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
NRM Module
1
Pm-12 (12V) Joining
Network
780 mW
1
Pm-24 (24V) Joining
Network
720 mW
1
PM-30 (12V) Joining
Network
960 mW
1
Содержание ROC809
Страница 6: ...ROC800 Series Instruction Manual vi Revised July 2017 Index I 1 ...
Страница 124: ...ROC800 Series Instruction Manual 4 38 Input Output Modules Revised July 2017 This page is intentionally left blank ...
Страница 156: ...ROC800 Series Instruction Manual 6 16 Troubleshooting Revised July 2017 This page is intentionally left blank ...
Страница 176: ...ROC800 Series Instruction Manual B 10 Wiring Diagrams Revised July 2017 This page is intentionally left blank ...