ROC800-Series Instruction Manual
5-10
Communications
Revised July-2017
LOI
– Local Port EIA-232 (RS-232D). Refer to
Section 5.5, Local
Operator Interface
.
Built-in
– Comm2 EIA-232 (RS-232C).
Module
– Comm3 to Comm5 EIA-232 (RS-232C).
EIA-232 (RS-232) uses point-to-point asynchronous serial
communication and is commonly used to provide the physical interface
for connecting serial devices, such as gas chromatographs and radios to
the ROC800-Series. EIA-232 (RS-232) communication provides
essential hand-shaking lines required for radio communication, such as
DTR and RTS.
EIA-232 (RS-232) communication includes LED indicators that display
the status of the Receive (RX), Transmit (TX), Data Terminal Ready
(DTR), and Ready To Send (RTS) control lines.
Table 5-6
defines the built-in EIA-232 (RS-232) terminals at the
Comm2 port and their function signals.
Table 5-6. Built-in EIA-232 (RS-232) Signal Routing – Comm2
Signal
LED Function
Terminal
RX
Lit when Comm2 is currently receiving.
1
TX
Lit when Comm2 is currently transmitting.
2
RTS
Lit when Comm2 request to send is active.
3
DTR
Lit when Comm2 data terminal ready is active.
4
GND
Common.
5
The EIA-232 (RS-232) communication module provides EIA-232 (RS-
232C) signals on the Comm3, Comm4, or Comm5 port depending on
where you have installed the module. Refer to
Table 5-7
.
Table 5-7. EIA-232 (RS-232) Communication Module Signal Routing – Comm3, Comm4, and Comm5
Signal
LED Function
Terminal
RX
Lit when module (Comm3, Comm4, or Comm5) is
currently receiving.
1
TX
Lit when module (Comm3, Comm4, or Comm5) is
currently transmitting.
2
RTS
Lit when module (Comm3, Comm4, or Comm5)
request to send is active.
3
DTR
Lit when module (Comm3, Comm4, or Comm5)
data terminal ready is active.
4
GND
Common.
5
5.8
EIA-422/485 (RS-422/485) Serial Communications Module
EIA-422/485 (RS-422/485) communication modules meet all EIA-
422/485 (RS-422/485) specifications for differential, asynchronous
serial communication transmissions of data over distances of up to 1220
meters (4000 feet). EIA-485 (RS-485) communication is commonly
Содержание ROC809
Страница 6: ...ROC800 Series Instruction Manual vi Revised July 2017 Index I 1 ...
Страница 124: ...ROC800 Series Instruction Manual 4 38 Input Output Modules Revised July 2017 This page is intentionally left blank ...
Страница 156: ...ROC800 Series Instruction Manual 6 16 Troubleshooting Revised July 2017 This page is intentionally left blank ...
Страница 176: ...ROC800 Series Instruction Manual B 10 Wiring Diagrams Revised July 2017 This page is intentionally left blank ...