ROC800-Series Instruction Manual
Revised July-2017
Input/Output Modules
4-25
Note
:
Pay close attention to the connections; do not reverse the
power wires.
Make
these connections only
after removing
power
from the ROC800. Double-check connections for the
proper orientation before applying power. If the connections are
reversed and power is applied, you may damage
both
the MVS
module and the ROC800-Series processor board.
Caution
You can induce ground loops by tying commons from various modules
together.
.
4088B Transmitter
The 4088B is Remote Automation Solutions’ latest transmitter
product. Designed as a drop-in replacement for the MVS205 sensor,
you use ROCLINK 800 to configure and (if necessary) calibrate the
module.
Refer to the following figure to correctly wire up to six 4088B
transmitters to the MVS I/O module.
A
121
customer-supplied resistor
B
121
customer-supplied resistor placed on ending sensor
Figure 4-31. MVS I/O to 4088B Wiring
Note
:
For RTD wiring, refer to
Section 2
of the
Rosemount 4088
MultiVariable™ Transmitter Reference Manual
(00809-0100-
4088, Rev BA, January 2015) (part D301770X012).
A
B
Содержание ROC809
Страница 6: ...ROC800 Series Instruction Manual vi Revised July 2017 Index I 1 ...
Страница 124: ...ROC800 Series Instruction Manual 4 38 Input Output Modules Revised July 2017 This page is intentionally left blank ...
Страница 156: ...ROC800 Series Instruction Manual 6 16 Troubleshooting Revised July 2017 This page is intentionally left blank ...
Страница 176: ...ROC800 Series Instruction Manual B 10 Wiring Diagrams Revised July 2017 This page is intentionally left blank ...