4.16 General
4.16.1 120V User I/O control terminal specifications
4.16.2 24 Vdc/Analog control terminal specification
C6
Digital input 1
C8
Digital input 2
C10
Digital input 3
C12
Digital input 4
C14
Digital input 5
C4
Digital input 6
Terminal C4 default function
External trip input
Terminal C6 default function
Not Stop
Terminal C8 default function
Run
Terminal C10 default function
Jog
Terminal C12 default function
Forward/Reverse
Terminal C14 default function
Reset
Type of input
120 Vac digital logic inputs
Maximum input voltage
132 Vac 50/60 Hz
Nominal input voltage range
96 Vac to 132 Vac
(120 Vac, +10% / -20%)
Nominal input frequency range
47 Hz to 53 Hz or
56 Hz to 63 Hz
Voltage for ON state
79 Vac to 132 Vac
Current for ON state
2 mA to 3 mA
Voltage for OFF state
0 Vac to 20 Vac
Current for OFF state
0 mA to 1.5 mA
On fast update time
16.5 ms
Off fast update time
24.5 ms
C1
120 Vac user output
C3
120 Vac user output
C5
120 Vac user output
C7
120 Vac user output
C9
120 Vac user output
C11
120 Vac user output
C13
120 Vac user output
Terminal C1 Function
Supply for user external trip
(E-Stop) terminal C2
Terminal C3 Function
Supply for user external trip (Interlocks)
terminal C4
Terminal C5 Function
Supply for user Not Stop
terminal C6
Terminal C7 Function
Supply for user Run terminal C8
Terminal C9 Function
Supply for user Jog terminal C10
Terminal C11 Function
Supply for user Forward/Reverse
terminal C12
Terminal C13 Function
Supply for user Reset
terminal C14
Nominal output voltage
120 Vac
Maximum output current
250 mA total for all 120 Vac outputs
Protection
Fuse
C15
120 Vac Relay output neutral
Terminal C15 Function
120 Vac Neutral connection point for
C16 relay output
C16
120 Vac relay output
Terminal C16 function
Contactor enable (Drive ON)
Nominal output voltage
120 Vac
Update time ON
16.5 ms
Update time OFF
24.5 ms
Maximum output current
250 mA total for all 120 Vac outputs
Protection
Fuse
1
0V common
Function
Common connection for all external
devices
2
+24V external input
Function
To supply the control circuit
without providing a supply to the
power stage
Nominal voltage
+24.0 Vdc
Minimum continuous operating
voltage
+19.2 Vdc
Maximum continuous operating
voltage
+30.0 Vdc
Minimum start-up voltage
21.6 Vdc
Recommended power supply
60W 24 Vdc nominal
Recommended fuse
3A, 50 Vdc
3
0V common
Function
Common connection for all external
devices
4
+10V user output
Function
Supply for external analog devices
Voltage tolerance
1%
Nominal output current
10 mA
Protection
Current limit and trip @12 mA