148
Quantum MP User Guide
www.emersonct.com Issue: A4
12.1.10 Altitude
Altitude range: 0 to 3,000m (9,900 ft), subject to the following conditions:
1,000m to 3,000m (3,300 ft to 9,900 ft) above sea level: de-rate the
maximum output current from the specified figure by 1% per 100m
(330 ft) above 1,000m (3,300 ft)
For example at 3,000m (9,900ft) the output current of the drive would
have to be de-rated by 20%.
12.1.11 IP Rating
The Quantum MP size 1 is rated to IP20 pollution degree 2 (dry, non-
conductive contamination only) except around the top of the drive where
the IP rating is IP00.The Quantum MP size 2 is rated IP00.
The IP rating of a product is a measure of protection against ingress and
contact to foreign bodies and water. It is stated as IP XX, where the two digits
(XX) indicate the degree of protection provided as shown in Table 12-6.
Table 12-6 IP Rating degrees of protection
12.1.12 Corrosive gasses
Concentrations of corrosive gases must not exceed the levels given in:
•
Table A2 of EN 50178
•
Class 3C2 of IEC 60721-3-3
This corresponds to the levels typical of urban areas with industrial
activities and/or heavy traffic, but not in the immediate neighborhood of
industrial sources with chemical emissions.
12.1.13 RoHS compliance
Quantum MP meets EU directive 2002-95-EC for RoHS compliance.
12.1.14 Vibration
Maximum recommended continuous vibration level 0.14 g r.m.s. broad-
band 5 to 200 Hz.
This is the limit for broad-band (random) vibration. Narrow-band
vibration at this level which coincides with a structural resonance could
result in premature failure.
Bump Test
Testing in each of three mutually perpendicular axes in turn.
Referenced standard:IEC 60068-2-29: Test Eb:
Severity: 18g, 6 ms, half sine
No. of Bumps: 600 (100 in each direction of each axis)
Random Vibration Test
Testing in each of three mutually perpendicular axes in turn.
Referenced standard:IEC 60068-2-64: Test Fh:
Severity: 1.0 m²/s³ (0.01 g²/Hz) ASD from 5 to 20 Hz
-3 dB/octave from 20 to 200 Hz
Duration: 30 minutes in each of 3 mutually perpendicular axes.
Sinusoidal Vibration Test
Testing in each of three mutually perpendicular axes in turn.
Referenced standard: IEC 60068-2-6: Test Fc:
Frequency range: 5 to 500 Hz
Severity: 3.5 mm peak displacement from 5 to 9 Hz
10 m/s² peak acceleration from 9 to 200 Hz
15 m/s² peak acceleration from 200 to 500 Hz
Sweep rate: 1 octave/minute
Duration: 15 minutes in each of 3 mutually perpendicular axes.
EN 613800-5-1:2007, Section 5.2.6.4. referring to IEC 60068-2-6
Frequency range:
10-150 Hz
Amplitude:
10-57 Hz @ 0.075mm pk
57-150 Hz @ 1g pk
Sweep rate:
1 octave/minute
Duration:
10 sweep cycles per axes in each of 3
mutually perpendicular axes
Shock Test
BS EN 60068-2-27, Test Ea
Pulse shape:
half-sine
Severity:
15g pk acceleration, 11 ms pulse duration
No of shocks:
3 in each direction of 3 mutually
perpendicular axes (total of 18)
12.1.15 Start up time
This is the time taken from the moment of applying power to the drive, to
the drive being ready to run a motor:
All sizes: 3s
12.1.16 Output speed range
Speed range: 0 to 10,000rpm
12.1.17 Accuracy
Estimated speed mode accuracy: Typically 5 to 10%.
Other modes are dependent on feedback device used.
12.1.18 Acoustic noise
The heatsink fan generates the majority of the acoustic noise produced by
the drive. The heatsink fan on the Quantum MP is a single speed fan.
Table 12-7 gives the acoustic noise produced by the drive.
Table 12-7 Acoustic noise data
12.1.19 Overall dimensions
Refer to section 3.4
First digit
Second digit
Protection against contact and
ingress of foreign bodies
Protection against ingress of water
0 No protection
0
No protection
1
Protection against large
foreign bodies
> 50mm
(large area contact with the
hand)
1
Protection against vertically
falling drops of water
2
Protection against medium
size foreign bodies
> 12mm
(finger)
2
Protection against spraywater
(up to 15° from the vertical)
3
Protection against small
foreign bodies
> 2.5mm
(tools, wires)
3
Protection against spraywater
(up to 60
from the vertical)
4
Protection against granular
foreign bodies
> 1mm (tools,
wires)
4
Protection against splashwater
(from all directions)
5
Protection against dust
deposit, complete protection
against accidental contact.
5
Protection against heavy
splash water (from all
directions, at high pressure)
6
Protection against dust
ingress, complete protection
against accidental contact.
6
Protection against deckwater
(e.g. in heavy seas)
7 -
7
Protection against immersion
8 -
8
Protection against submersion
IP rating
It is the installer’s responsibility to ensure that any enclosure
which allows access to drives while the product is energized,
provides protection against contact and ingress in the
requirements for IP20.
WARNING
NOTE
Model
SPL at 1m (dBA)
QMP45A4(R)
No fans installed
QMP75A4(R)
43
QMP155A4(R) - QMP210A4(R)
56
QMP 350A4(R) - QMP700A4(R)
68