136
Quantum MP User Guide
www.emersonct.com Issue: A4
Parameter
Range(
)
Default(
)
Type
14.01
PID output
±100.00%
RO Uni
NC PT
14.02
PID source1
Pr
0.00
to
22.99
Pr
0.00
RW Uni
PT US
14.03
PID source 2
Pr
0.00
to
22.99
Pr
0.00
RW Uni
PT US
14.04
PID source 3
Pr
0.00
to
22.99
Pr
0.00
RW Uni
PT US
14.05
PID source invert 1
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.06
PID source invert 2
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.07
PID reference slew rate limit
0 to 3200.0s
0.0
RW Uni
US
14.08
PID enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.09
PID optional enable source
Pr
0.00
to
22.99
Pr
0.00
RW Uni
PT US
14.10
PID P gain
0 to 4.000
1.000
RW Uni
US
14.11
PID I gain
0 to 4.000
0.500
RW Uni
US
14.12
PID D gain
0 to 4.000
0.000
RW Uni
US
14.13
PID upper limit
0 to 100.00%
100.00
RW Uni
US
14.14
PID lower limit
±100.00%
-100.00
RW
Bi
US
14.15
PID scaling
0 to 4.000
1.000
RW Uni
US
14.16
PID destination
Pr
0.00
to
22.99
Pr
0.00
RW Uni
PT US
14.17
PID hold integrator
OFF (0) or On (1)
OFF (0)
RW Bit
NC
14.18
PID symmetrical limit enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
14.19
PID main reference
±100.00%
RO
Bi
NC PT
14.20
PID reference
±100.00%
RO
Bi
NC PT
14.21
PID feedback
±100.00%
RO
Bi
NC PT
14.22
PID error
±100.00%
RO
Bi
NC PT
RW
Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save