User Manual
Chapter 3
GFK-2721B
Sep 2019
Configuration
32
Catalog #
Description
Parameter
Jumper
Setting
IC200ALG321 Analog Output Module, 12 Bit
Voltage 4 Channels. 0 to +10 VDC
Range
Outputs default to 0 V
B13 - B14
Outputs default to hold last state no jumper
IC200ALG322 Analog Output Module, 12 Bit
Voltage 4 Channels. -10 to +10
VDC Range
Same as IC200ALG321
IC200ALG325 Analog Output Module, 13 Bit
Voltage 8 Channels
0Vdc to 10Vdc,
outputs default to 0Vdc
B1 - B2,
and B2 - B3
0Vdc to 10vdc
outputs default to hold last state
B1 - B2
-10Vdc to +10 Vdc outputs default
to 0Vdc
B2 - B3
-10Vdc to +10 Vdc outputs default
to hold last state
no jumper
IC200ALG326 Analog Output Module, 13 Bit
Current 8 Channels
0mA to 20 mA outputs default to
0mA
B1 - B2, and
B2 - B3
0mA to 20 mA outputs default to
hold last state
B1 - B2
4mA to 20 mA outputs default to
4mA
B2 - B3
4mA to 20 mA outputs default to
hold last state
no jumper
IC200ALG327 Analog Output Module, 13 Bit
Voltage 12 Channels
Same as IC200ALG325
IC200ALG328 Analog Output Module, 13 Bit
Current 12 Channels
Same as IC200ALG326
IC200ALG430 Analog Mixed Module, Input
Current 4 Channels, Output
Current 2 Channels
Same as IC200ALG320
IC200ALG431 Analog Mixed Module, 0 to
+10VDC Input 4 Channels,
Output 0 to +10VDC 2 Channels
Same as IC200ALG321
IC200ALG432 Analog Mixed Module, 12 Bit -10
to +10VDC, Input 4 Channels /
Output -10 to +10VDC 2
Channels
Same as IC200ALG321
3.3
Assigning IO-Device Names
After the PROFINET Scanner and other IO-Devices on the LAN have been entered the
configuration, a Discovery and Configuration Protocol (DCP) tool must be used to assign a
name to each IO-Device. The Name of each device on the LAN must match the
configuration. This step is required before downloading the configuration from the