4.3.3
Review relay settings
This is a read-only mode to provide a summary of the relay settings. Changes to the relay
settings cannot be made in this menu item.
Procedure
1.
Press and hold the Setup button or the magnet to the Reed switch to enter the main
menu; wait for the countdown, from 10 to 0, to end.
2.
Release the Setup button or remove the magnet from the Reed switch.
The current output will move to 3.0 mA.
3.
When
Review Relay Settings
and then
YES?
is displayed press the Setup button or use
the Reed switch to select this option.
A flashing YES confirms the selection and the settings will be displayed.
4.3.4
Set relay options
This section outlines how to change the normal operation of the
Clean Window
and
Alarm
relays.
Follow the steps below to alter the relay functions or refer to
Figure 4-2
.
Note
The
Fault Alarm
relay settings are fixed as normally
Energized
and
Non-Latching
and are not adjustable
within the menu system.
Procedure
1.
Press and hold the Setup button or the magnet to the Reed switch to enter the main
menu; wait for the countdown, from 10 to 0, to end.
2.
Release the Setup button or remove the magnet from the Reed switch.
The current output will move to 3.0 mA.
3.
When
Set Relay Options
and then
YES?
is displayed, press the Setup button
or use the Reed switch to select.
A flashing
YES
will confirm your selection. The message
Set Clean Window
Alarm
and then
YES?
will be displayed.
4.
Press the Setup button or use the Reed switch to select this option.
The flashing
YES
will confirm this selection. After the
Clean Window Alarm
option has
been chosen the message
Coil Status
will be displayed followed by
Energized
YES?
.
5.
ii) To select that the relay be energized under normal conditions, press the Setup
button or use the Reed switch to select this option.
Programming
30
Содержание Net Safety Millennium
Страница 1: ...Reference Manual FGD MAN 0077 Rev 7 July 2017 Millennium APM Oil Mist Detector Air Particle Monitor ...
Страница 4: ......
Страница 8: ...Contents iv ...
Страница 14: ...Transmitter Dimensions Figure 2 3 Junction Box Sensor Dimensions Figure 2 4 Installation 6 ...
Страница 34: ...Operation 26 ...
Страница 42: ...Programming flowchart Figure 4 2 Programming 34 ...
Страница 46: ...Maintenance 38 ...
Страница 48: ...Electrostatic sensitive device 40 ...
Страница 50: ...Wire resistance table 42 ...
Страница 54: ...Specifications 46 ...
Страница 60: ...Ordering information 52 ...
Страница 61: ...Ordering information 53 ...
Страница 62: ...Ordering information 54 ...
Страница 63: ...Ordering information 55 ...