5
Maintenance
5.1
Response check
It is recommended that the APM be checked and tested at least once every three months.
Spray Smoke Detector Tester (or equivalent product) in the direction of the sensor from a
distance of two feet. Typically, a one to two second burst is adequate to initiate an alarm.
When the alarm activates, the display will read
Alarm
, the Status LED will flash red, and the
current output will be 20.0 mA to indicate detection of particulate matter or canned
contaminant.
After simulation, reset the alarm if latched as outlined in
Section 3.4
and zero the APM as
per
Section 4.3.1
in clear air free of particulates or at the accepted particulate background
level for the specific application.
Note
The overuse of artificial particulate detector testers or spraying from too close a range may impair
the operation of the APM due to the accumulation of an oily film on the internal window.
5.2
Cleaning
The APM Sensor should be routinely cleaned. The frequency of cleaning will depend on the
application and environment where the APM is installed.
When the
Dirty Chamber
or
Clean Window Alarm
message is displayed, the lens / window
and chamber will require cleaning. Follow the steps below when cleaning.
Procedure
1.
Turn off power to the transmitter.
2.
Unscrew bolts at the end of circular plate and connecting rods.
3.
Using the included window cleaning kit (HDW-0061), clean the inner sides of the
sensor chamber and front side of the lens / window.
4.
Ensure that there is no residue left on the lens or window.
5.
Put the circular plate back into position, ensuring that the textured surface faces the
APM window, and screw in the bolts at the end of the connecting rods.
6.
Return power to the APM and check for normal operation.
7.
Complete the Zero procedure to establish new settings.
If problems develop and persist, contact Net Safety Service department or refer to
Section 1.3
(Return of material).
Maintenance
35
Содержание Net Safety Millennium
Страница 1: ...Reference Manual FGD MAN 0077 Rev 7 July 2017 Millennium APM Oil Mist Detector Air Particle Monitor ...
Страница 4: ......
Страница 8: ...Contents iv ...
Страница 14: ...Transmitter Dimensions Figure 2 3 Junction Box Sensor Dimensions Figure 2 4 Installation 6 ...
Страница 34: ...Operation 26 ...
Страница 42: ...Programming flowchart Figure 4 2 Programming 34 ...
Страница 46: ...Maintenance 38 ...
Страница 48: ...Electrostatic sensitive device 40 ...
Страница 50: ...Wire resistance table 42 ...
Страница 54: ...Specifications 46 ...
Страница 60: ...Ordering information 52 ...
Страница 61: ...Ordering information 53 ...
Страница 62: ...Ordering information 54 ...
Страница 63: ...Ordering information 55 ...