5
Reference Manual
24625020, Rev AA
March 2017
Figure 1-2. High Water Level Detection in Drain Pot
A. Superheat steam line.
D. Drain line.
B. Drain pot.
E. High alarm signal.
C. Isolation valve.
F. In-line manifold with two electrodes (channels 1 and 2).
1.5.2
Water level detection in a boiler drum
A Hydratect 2462 system for detecting high and low water levels in a boiler drum is shown
in
.
Trip signals are validated by connecting both Hydratect channels using a “two-out-of-two”
configuration in a Hydratect 2462 Electronics Control Unit. For example, the high-level trip
signal occurs only when water is detected at both the high and the high-high water level
electrodes. Further information is in
Section 3: Installing the Electronics Control Unit
.
The illustrated Hydratect 2462 system uses a sidearm manifold for detecting intermediate
water levels between high and low. Connection information for the manifold pipework is in
Note the following points:
The connecting pipework must be sloped as indicated in
This is done to ensure a flow of condensate through the manifold.
The isolating valves, when opened, should allow unrestricted flow through the
manifold. Globe valves are highly recommended. These valves should be installed
with the handle spindle horizontal.
The connecting pipework must be insulated, as shown by the dashed lines marked
in
.
A
B
C
D
C
F
E
Содержание Mobrey Hydratect 2462
Страница 1: ...Reference Manual 24625020 Rev AA March 2017 Mobrey Hydratect 2462 Steam Water Detection System ...
Страница 2: ......
Страница 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Страница 26: ...20 Reference Manual 24625020 Rev AA Installing the electrodes March 2017 Installing the electrodes ...
Страница 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Страница 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Страница 65: ......