Installation summary
The basic steps to installing the Hydratect 2462 Electronics Control Unit (“Control Unit”)
are as follows:
1.
Fit cable glands to the bottom of the Control Unit.
For this, holes need to be cut through 1.6 mm of stainless steel. The required hole
sizes depend on the gland type to be fitted.
“Fitting cable glands” on page 22
for further information.
2.
Mount the Control Unit, taking into consideration:
a.
The Control Unit is to be bolted in position through two brackets (lugs)
). Fixing bolts are not supplied with the Control Unit.
b. The preferred site for the Control Unit is a wall or vertical bracket structure where
easy access is available for viewing and servicing, and of suitable composition and
load bearing ability to four times the control unit weight.
c.
The case must be bonded to ground (earth) through a suitably-rated cable and
grounding (earthing) point.
d. Control Unit mounting and grounding (earthing) procedures are in the section
“Mounting the Hydratect 2462 Control Unit” on page 23
3.
Select the various Hydratect 2462 system configuration options using the
‘jumpers’ (plug-links) on the internal printed circuit board (“PCB”).
“Setting the printed circuit board (PCB) jumpers” on page 23
for information.
4.
Prepare and connect cables to the front panel.
These cables are for the electrodes, fault and status relays, and power supplies.
When the status relay latch option is fitted, a connection is also required for the
latch reset input.
Cable connections are described in
“Connecting the electronics” on page 26
.
When the electrodes and the electronics control unit have been installed, the Hydratect
2462 system can be tested. The test procedure is in
.
Note
When re-securing the front panel of the electronics control unit with the four screws,
ensure the four washers make complete contact with the metalwork of the front panel. The
label (art work) on the front panel must not be trapped under these washers.
Содержание Mobrey Hydratect 2462
Страница 1: ...Reference Manual 24625020 Rev AA March 2017 Mobrey Hydratect 2462 Steam Water Detection System ...
Страница 2: ......
Страница 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Страница 26: ...20 Reference Manual 24625020 Rev AA Installing the electrodes March 2017 Installing the electrodes ...
Страница 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Страница 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Страница 65: ......