23
Reference Manual
24625020, Rev AA
Installing the Electronics Control Unit
March 2017
Installing the Electronics Control Unit
3.3
Mounting the Hydratect 2462 Control Unit
To protect the printed circuit boards (PCBs), the Hydratect 2462 Electronics Control Unit
(“Control Unit”) must be mounted without the front panel fitted.
Mounting procedure
Note
The Control Unit weight is 2.8 kg (6.2 lb). To conform to safety requirements, the wall or
vertical bracket structure on which the Control Unit is mounted must be of a suitable
composition and load bearing ability to support four times this weight.
1.
Select a suitable location for the Control Unit, taking into consideration:
a.
Cable length restrictions.
b. Relative positions of the electrodes.
c.
Accessibility for viewing and servicing.
d. Composition and load bearing ability of the wall to support four times the weight
of the control unit.
2.
Prepare the fixing points (for screws, bolts, etc.) using the dimensions of the fixing
brackets shown in
.
3.
Mount the Control Unit to the wall by screwing or bolting through the brackets.
4.
Connect the ground (earth) stud to a suitable grounding (earthing) point.
This connection must have a rating of 25 A.
3.4
Setting the printed circuit board (PCB) jumpers
Various configuration options on the front panel PCB can be selected by using ‘jumpers’
(1)
that plug into a DIL pin strip headers labeled PL203 and PL403.
The configuration options are:
Normal condition for steam/water detection (normal-steam or normal-water).
Threshold for steam/water detection (high or low sensitivity).
Electrode contamination detection (disabled or enabled).
Electrode contamination detection (high or low sensitivity).
Operation of status relay (latched or non-latching).
shows all options and their jumper settings on the DIL pin strip header.
When the Control Unit is shipped from the factory, PCB jumpers are set to a default
configuration as shown in
.
The locations of PCB jumpers for each of the channels are shown in
.
1.
A Jumper is a metal bridge that closes an electrical circuit. Typically, a jumper consists of a plastic plug that fits over a pair of protruding
pins. By placing a jumper plug over a different set of pins, you can change a board's parameters.
Содержание Mobrey Hydratect 2462
Страница 1: ...Reference Manual 24625020 Rev AA March 2017 Mobrey Hydratect 2462 Steam Water Detection System ...
Страница 2: ......
Страница 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Страница 26: ...20 Reference Manual 24625020 Rev AA Installing the electrodes March 2017 Installing the electrodes ...
Страница 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Страница 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Страница 65: ......