39
Reference Manual
24625020, Rev AA
March 2017
Section 4
System
Testing
4.1
Test summary
contains the procedures for testing the two basic configurations of the Hydratect
2462 system: (1) water-normal and (2) steam-normal
Use the procedures to check the operation of the Hydratect 2462 system after installation
completion or any configuration change. In each procedure, checking includes the
detection sensitivities and the latched fault relay facility.
The test equipment required is minimal and depends to some extent on the ancillary
equipment installed in your system. You will need:
A resistor to simulate steam presence:
10 M
A resistor to simulate water presence:
56 k
(low sensitivity) or 120 k
(high sensitivity).
A resistor to simulate electrode contamination:
270
(low sensitivity) or 820
(high sensitivity).
A fault relay reset push-button.
(This is required only when the latched relay option is configured).
A device, such as a lamp or beeper.
(This is to check the operation of the output contacts. The contact ratings are given
in
Appendix A: Specifications and Data
Where ancillary equipment is already connected to the output contacts, and may
safely be used, it may be more appropriate to check the contact operation with
that equipment.
Содержание Mobrey Hydratect 2462
Страница 1: ...Reference Manual 24625020 Rev AA March 2017 Mobrey Hydratect 2462 Steam Water Detection System ...
Страница 2: ......
Страница 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Страница 26: ...20 Reference Manual 24625020 Rev AA Installing the electrodes March 2017 Installing the electrodes ...
Страница 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Страница 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Страница 65: ......