45
Reference Manual
24625020, Rev AA
March 2017
17.
Reconnect the white conductor.
If the Status Relay Operation setting is set to latched, the Control Unit must be
power cycled to set the status relay back to the energized position.
Check that the LEDs, and fault and status relays, have returned to their original
states as shown in steps
and
18.
Disconnect the black conductor (lead) from ground by removing the screw
securing it to the manifold or, if using an insert, by removing the electrode cover
base plate.
19.
Check the front panel LED states are as expected:
!
LED on
STEAM
LED on
WATER
LED off
20.
Check the fault and status relays are as expected:
a.
Fault relay de-energized
b. Status relay energized
21.
Reconnect the black conductor (lead).
Check the front panel LEDs, and fault and status relays, have returned to their
original states as shown in steps
.
22.
Replace and secure the electrode cover.
23.
Remove the safety function bypass and otherwise restore normal operation.