This screen displays the following information:
•
a chart at the top of the screen showing a typical curve for a discharge,
charge and boost charge cycle,
•
description of the terminology used in the chart at the bottom of the
screen,
•
a “Voltage Boost Status” box to activate or deactivate the voltage boost
function,
•
a “General Voltage Boost Settings” box in which to enter the voltage
boost level,
•
a “Manual Voltage Boost Settings” box in which to enter the manual
voltage boost duration,
•
an “Automatic Voltage Boost Settings” box in which to enter the
automatic voltage boost factor, and
•
a “Cyclic Voltage Boost Settings” box in which to enter the cyclic
voltage boost parameters.
Clicking on the
button in the “Voltage Boost Status” box will
enable the voltage boost function. The “Voltage Boost Function” field and
button text will then change from
to
and
an
button will be added near the “Operate Voltage Boost” field, as
shown in the following screen.
Screen 21
The voltage boost function is then enabled and ready to operate in the three
modes:
•
An automatic boost will be started automatically as the rectifiers resume
their operation after an AC mains failure. The duration of the voltage
boost will be the duration of the AC mains failure times the factor value
programmed in the “Automatic Voltage Boost Settings” box.
•
A cyclic boost will be started automatically at every interval and for the
duration programmed in the Cyclic Voltage Boost Settings” box.