Protection device configurations for the loads:
•
up to six 1 A to 100 A single-pole circuit breakers or 1 A to 50 A fuses,
or
•
up to three 1 A to 100 A single-pole circuit breakers or 1 A to 50 A
fuses and one 10-position (SAN-O) fuse kit for fuses ranging from
0.180 A to 20 A or one 8-position (GMT) fuse kit for fuses ranging
from 0.180 A to 15 A, or
•
up to two 10-position (SAN-O) fuse kits for fuses ranging from
0.180 A to 20 A, or
•
up to two 8-position (GMT) fuse kits for fuses ranging from 0.180 A to
15 A.
3.2.5.3. Controller interface card
The controller interface card is a printed circuit board mounted behind the
front panel of the Lorain CIP shelf. This board is equipped with three
terminal blocks and a connector used for wiring interface between the
controller and outside circuitry such as a battery temperature probe, an
external fuse alarm signal, and an external battery fuse alarm signal (–48 V dc
signals are required to activate the fuse and battery fuse alarms).
Figure 3.15 – Connecting details on the controller interface card
Note:
In Europe, ferrite beads may be required around signal wires and/or
cables (alarms, temperature probe, etc.) at the point of entry in the Lorain
CIP shelf, depending on the configuration, in order to meet European EMI
requirements.