Note 12:
On an 8-position (GMT) fuse kit, fuses rated at 10A or greater
must have their adjacent positions left empty (dummy fuse installed in
empty position), and load must not exceed 70% of device rating.
CAUTION
Prevent damage to load clips.
The load clips are made of plastic material and it is therefore
important to use a torque wrench and to apply no more than
the required torque value (4.25 ft/lb or 5.75 N-m) to prevent
damage to the clips.
Figure 3.13 illustrates a perspective view of the distribution section inside the
Lorain CIP shelf, the connecting points on the controller interface card at the
back of the front panel, and the front panel of the System Manager CIP,
which rotates to allow access to the protection devices inside the shelf.
Figure 3.13 – Perspective view of Lorain CIP distribution section
Figure 3.14 illustrates the typical cabling for a distribution configuration
using three circuit breakers and one 10-position (SAN-O) fuse kit.