Wiring Connections
25
8.0 W
IRING
C
ONNECTIONS
!
WARNING
Verify that all incoming high and low voltage power circuits are de-energized and locked out
before installing cables or making electrical connections.
All power connections must be completed by a licensed electrician experienced in wiring UPS
equipment and in accordance with all applicable national and local electrical codes.
Improper wiring may cause damage to the UPS or injury to personnel.
!
CAUTION
All shielded cables, non-shielded cables, non-shielded control wires, non-shielded battery
breaker control wires and non-shielded remote control wires must be housed in individual,
separate, steel conduits. Placing multiple cables in the same conduit with other control or
power wiring may cause system failure.
NOTE
Use appropriately sized wire as a grounding conductor. Solid metal conduit is not a suitable
ground conductor for UPS systems and could negatively affect system performance.