![Emerson Liebert Series 610 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/emerson/liebert-series-610/liebert-series-610_manual_104964013.webp)
DISCONTINUED
PRODUCT
Equipment Location
7
4.0 E
QUIPMENT
L
OCATION
1. Handle cabinet(s) in accordance with the safety precautions in this manual, especially in these
sections:
•
Battery Cabinet Precautions
—inside front cover
•
Important Safety Instructions
—page 1
•
2.0 - Unloading and Handling
—page 5
•
5.0 - Battery Installation
—page 8
Use a suitable material handling device to move cabinet to its final location.
Exercise extreme
care because of the uneven weight distribution.
Carefully lower the cabinet to the floor.
2. Verify that the UPS system is installed in a clean, cool and dry location.
3. Installation and serviceability will be easier if adequate access is provided on all sides of the
equipment, but only front access is required.
a. Verify that there is adequate clearance to open cabinet doors—4 ft. (1.2m) is recommended.
NEC requires sufficient clearance in front of the equipment to fully open all doors without
restriction. See drawings and local codes.
b. Verify that there is adequate area in front of circuit breakers to perform maintenance. Check
installation drawings for location of breakers. Check with local codes.
c. Verify that there is adequate clearance above all cabinets to allow exhaust air to flow without
restriction. The minimum clearance is 2 ft. (0.6m), unobstructed by conduit or any other
items. Liebert recommends against using top-feed air conditioning systems.
4. Align the UPS cabinet, battery cabinets (if used) and optional transformer and maintenance
bypass cabinets, as shown in the Line-Up Detail drawings (
Figures 18
,
19
,
20
,
22
,
23
and
26
through
29
) and your submittal package.
5. Connect the cabinets, internal cables and busbars, if applicable. Internal control connections
should be left disconnected for later installation by Liebert LGS Customer Engineers.
Содержание Liebert Series 610
Страница 6: ...DISCONTINUED PRODUCT iv ...
Страница 42: ...DISCONTINUED PRODUCT Installation Drawings 36 Figure 17 Battery power pack system 88 797616 03 Rev 08 ...
Страница 43: ...DISCONTINUED PRODUCT Installation Drawings 37 Figure 18 Battery power pack Size A 88 797616 01 Rev 10 ...
Страница 70: ...DISCONTINUED PRODUCT Installation Drawings 64 ...
Страница 75: ...DISCONTINUED PRODUCT ...