Configuring Your Neutral and Ground Connections
16
6.4
Alternate Grounding Configuration, Non-Isolated
A few applications in this power range have 208 VAC input and output, and a connected load consist-
ing of multiple Power Distribution Units (PDUs), panelboards, switchboards or other items of load
equipment which do not have isolation transformers.
Notice in
Figure 4
that the UPS module main input and bypass input are connected to a grounded-
wye service. In this configuration, the UPS module is not considered a separately derived source.
The UPS module output neutral and the load neutral are solidly connected to the building service
neutral, which is bonded to the grounding conductor at the service entrance equipment.
Figure 4 Alternate grounding configuration, non-isolated
This arrangement may be used for systems with 208 VAC input and output. However, it does not pro-
vide any isolation or common-mode noise attenuation for sensitive loads. For this reason, this config-
uration is not a preferred installation method.
NOTE
If there is a 4-pole Automatic Transfer Switch (ATS) between the service entrance and the UPS,
this configuration cannot be used. Refer to
6.3 - Preferred Grounding Configuration With
Isolated Bypass
to determine a suitable configuration.
GROUNDING
ELECTRODE
PER NEC 250-24
Содержание Liebert Series 610
Страница 6: ...DISCONTINUED PRODUCT iv ...
Страница 42: ...DISCONTINUED PRODUCT Installation Drawings 36 Figure 17 Battery power pack system 88 797616 03 Rev 08 ...
Страница 43: ...DISCONTINUED PRODUCT Installation Drawings 37 Figure 18 Battery power pack Size A 88 797616 01 Rev 10 ...
Страница 70: ...DISCONTINUED PRODUCT Installation Drawings 64 ...
Страница 75: ...DISCONTINUED PRODUCT ...