Product Specifications
Liebert NXC
9.6
Electrical Characteristics (Inverter Output)
Table 9-6Inverter Output (to Critical Load)
Item Unit
Rated power (kVA)
10 15 20
Rated AC voltage
1
Vac
3-In 3-Out: 230Vac ±1% 3 phase balanced
Frequency
2
Hz
50/60
Overload
60 min
%
105
5 min
%
125
1 min
%
150
< 200 ms
%
>150
Fault current
A (RMS)
91A for 200ms
Non-linear load capability
3
%
100
Load crest factor
-
3:1
Max. neutral current for non-linear load
A (RMS)
50
Steady state voltage stability
%
±1
Transient voltage response for 100%
rated linear load step
-
±5% within 60ms
Total harmonic voltage (0-100% load)
%
2% linear load; 5% non linear load
Synchronization window
%
Rated frequency ±8
Slew rate (max change rate of
synchronization frequency)
Hz/s
0.6 (single UPS), 0.2 (parallel system)
Note:
1
Factory set to 400V, 380V or 415V selectable by commissioning engineer.
2
Factory set to 50Hz, 60Hz selectable by commissioning engineer. Note that the system frequency can be changed only when the UPS is
on bypass. It is strictly prohibited to change the system frequency when the UPS is on inverter.
3
IEC 62040-3, annex E (crest factor 3:1).
9.7
Electrical Characteristics (Bypass Input)
Table 9-7 Bypass Input
Item Unit
Rated power (kVA)
10 15 20
Rated AC voltage
1
Vac
380/400/415, three-phase five-wire, sharing neutral with the rectifier input and
providing neutral reference to the output
Rated current
380V
400V
415V
A 16
23
30
A 15
22
29
A 14
21
28
Current rating of neutral cable
A
87
Overload
long time
%
105
5 min
%
125
1 min
%
150
1 s
%
400
< 200ms
%
>400
Frequency
2
Hz
50/60
Transfer time (between bypass and
inverter)
ms
Synchronous <2 ms
Asynchronous <20 ms (40, 60, 80, 100, 120 can be set)
Bypass voltage tolerance
%Vac
Upper limit: +10, +15 or +20; default: +15
Lower limit: -10, -20, -30 or -40; default: -20
Bypass frequency tolerance
%
±10
Synchronization window
%
Rated frequency ±8
Note:
1
Factory set to 400V, 380V or 415 V selectable by commissioning engineer.
2
Factory set to 50Hz, 60 Hz selectable by commissioning engineer.