54 Chapter 5 Operating Instructions
NX UPS Single Module And Parallel System 250kVA ~ 800kVA User Manual
Bypass switch Q2
Maintenance switch Q3
Main input switch Q1
Output switch Q5
(optional)
Figure 5-3 UPS power switch (600kVA ~ 800kVA)
5.1.3 Verifying DIP Switch Setting (600kVA ~ 800kVA)
Opening the front door of the main power cabinet reveals a 2-bit DIP switch, as shown in Figure 5-4. The DIP switch
sets the communication address of the main power cabinet, and it has been set in factory. The factory setting is: For
main power cabinet 1, bit 1 is set to ON, bit 2 is set to OFF (as shown in Figure 5-4); for main power cabinet 2, bit 1 is
set to OFF and bit 2 is set to ON. Before power-on, be sure to check that the settings of the DIP switches are
consistent with the factory settings.
Warning
Wrong DIP switch setting will lead to serious communication fault and even system power failure.