Chapter 10 Service And Maintenance 93
NX UPS Single Module And Parallel System 250kVA ~ 800kVA User Manual
Fixing screw
Fixing bar
Air filter
Fixing bar
Figure 10-1 Replacing air filter (250kVA ~ 400kVA, 600kVA ~ 800kVA)
For 500kVA ~ 600kVA E UPS, refer to Figure 10-2 for the air filter replacement procedures:
1. Open the front door of the UPS to reveal the air filters on the back of the front door.
2. Remove a fixing bar on outboard of the air filter to be replaced.
3. Remove the air filter, and insert a clean one.
4. Re-install the removed fixing bar in the original place.
Fixing screw
Fixing bar
Air filter
Fixing screw
Fixing bar
Air filter
Figure 10-2 Replacing air filter (500kVA ~ 600kVA E)