Teamwork
Liebert
®
iCOM
®
for Liebert DSE
™
82
4.3.8 Standby—Rotation
Typical Standby (Lead/Lag) Function
This function can be performed in any teamwork mode, including NO Teamwork.
One or more units can be defined to be Standby; the normal status of standby units is Standby Off
(fan off).
In case one regular unit has an alarm that is defined (to be defined in the alarm configuration), to
switch on a standby unit, the faulty unit will switch off and the standby unit will switch On.
If the next unit has an alarm, the next standby unit will be started. If no more standby units are
available, the unit with a non-critical alarm that permits unit operation will be switched On again
(water detection, fan alarm, fire alarm etc. will not permit unit restarting).
The standby function can be rotated daily (setting the time), weekly (setting the day of the week and
time) or monthly (setting the first weekday of the month and time).
The rotation is performed with a selectable number of units: if 1 is selected, to standby rotates from
1-2 to 2-3 in a 4 units configuration with two standby units, and rotates from 1-2 to 3-4 in the same
configuration, when the rotation parameter is set to 2.
Standby and Cascade
Cascade is possible in Teamwork Mode 1 and 3 only.
Line S508 Cascade Units has the options of Yes, Cool / Heat, Cooling, Fan
Yes
—Based on a call for heating, cooling, humidification or dehumidification.
Cool / Heat
—Based on a call for heating or cooling. Teamwork Mode 1
Cooling
—Based on a call for cooling. Teamwork Mode 1
Fan
—The only selection available for Teamwork Mode 3; not available in Teamwork Mode 1. Uses
fan control deviation to stage on standby unit fans / cooling. Fans stage serially according to the
system fan control band and temperature control is based on the local supply deviation. (Fan
proportional band / number of connected units)
The standby unit will remain On for the time set in the parameter. The default is 30 minutes; range is
from 2 to 360 minutes.
Standby units will start if an alarm occurs in one of the operational units. If the standby units are
cascaded or in Teamwork Mode 3, they will also start and work with the regular operational units if
the temperature or humidity cannot be controlled by the operational units; before a high or low
temperature / humidity condition occurs. Cascaded units are switched Off again as soon as the
temperature / humidity returns back to normal.
The master unit defines its proportional band according to the number of available units (see
When a standby unit receives a request for full heating or cooling from the master unit (see
), it will respond to the request after its control delay.
NOTE
Before entering standby mode, units may operate the fan only for 3 minutes if previously
calling for heat or humidification to cool components and remove steam from the unit.
NOTE
Cascaded units are not included in the calculation of the average temperature / humidity.