Service Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
158
Figure 143
Options setup, page 6 of 6
S457 Q15 Output Function
—Sets the output function for Q15. This parameter is selectable for 0 =
None, 1 = Dehum On, 2 = Cooling On, 3 = Reheat On, 4 = Comp On, 5 = Comp 1 On, 6 = Comp 2 On, 7
= Humi On, 8 = Fan On, 9 = FreeCool On, 10 = Damper, 11 = High Temp, 12 = Low Temp, 13 = Loss
Power and 14 = Power Source The default setting is none. NOTE: Unit Code 16 can set the output for
this parameter.
S458 Q15 output direction
—Sets the Q15 output direction. This parameter is adjustable from
direct or reverse. The default setting is direct.
S459 Fan delay for damper
—Sets the delay for damper output. This parameter is adjustable from
0 = Return, 1 = Supply, 2 = Rem Max, 3 = Rem Low and 4 = Rem Avg. The default setting is Return.
Sets the delay for the damper to open before the fan starts. This parameter is adjustable from 0 to 120
seconds.
S460 Damper switch feedback damper
—Sets the timer for the damper when using Q15. This
parameter is adjustable from 0 to 120 seconds. The default setting is 30 seconds.
S461 Q15 Temp output sensor
—Sets the output sensor when using Q15. This parameter is
adjustable from 0 to 120 seconds. The default setting is 30 seconds.
S462 Q15 Temp output threshold
—Sets the output threshold for the temperature using Q15. This
parameter is adjustable from 32°F to 150°F. The default setting is 80°F.
S463 Q15 temp actual
—Shows the status of the temperature in Celsius or Fahrenheit for Q15.
S465 Medium board: Q15 map to K11
—Shows the status of Q15 being mapped to K11 on the
medium board. This parameter will be shown as
No
or
Yes
. On the medium board, Q15 is mapped to
K11 and is selectable. If this has been selected, this parameter will show the status of K11.
S466 Q15 output state
—Shows the status of the Q15 output state. This parameter will be shown as
Off
or
On
.
Содержание Liebert iCOM