Service Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
140
Figure 122
iCOM-DO events setup screen, page 2 of 3
S733-740, S744-S751—The lines are divided into four columns.
•
Event Description
—Read-only parameter that describes the event type that may activate an
output on the Liebert iCOM-DO
™
. Each event description may reflect a status or alarm,
depending on the line.
•
ID
—Displays the number of the Liebert iCOM-DO. Currently only one Liebert iCOM-DO card is
supported. The ID must match the S721 to function.
•
Output #
—Shows which output is tied to a particular alarm. The default values are set to be the
same output as the Liebert ENV-DO
™
card, the predecessor to the Liebert iCOM-DO. The ID’s are
linked to S725.
•
Status
—Read-only value that shows the state of the output.
Figure 123
Liebert iCOM-DO events setup screen, page 3 of 3