Teamwork
81
Liebert
®
iCOM
®
for Liebert DSE
™
4.3.7 Software Setup
Cooling units to be set up for Teamwork Mode 3 (Liebert Optimized Aisle Control) must be connected
in a Liebert iCOM U2U network and must have:
• Digital scroll compressors, chilled water valves or four-step compressors. (Two-step semi-hermetic
compressors and standard scroll units cannot be configured for Teamwork 3.)
• Variable speed fans
• Supply air sensors connected for temperature control.
1. Go to the Service Menu > Remote Sensors and verify that all the connected 2T sensor readings are
shown.
2. Set the corresponding sensors’ nodes to either control or reference. These settings are based on
rack setup or customer preference.
3. Determine the appropriate setting for SB03 Unit Remote Sensor Mode/AVG incl. The values set
here will determine how the Liebert iCOM monitors inlet rack temperature to control the fans.
Max
: controls fan(s) based on the maximum rack temperature.
Average
: controls fan(s) based on an average rack temperature. The number of sensors to be used
to calculate the average is determined to the far right. If the number of sensors to be used to
calculate the average is less than the number of rack sensors programmed for control, the Liebert
iCOM will average only the highest sensor readings.
4. Set Service Menus > Setpoints S103 Temperature Control Sensor to
Supply
. This parameter must
be set at each unit.
5. Go to Service Menu > System/Network Setup S803 Teamwork Mode. Change the value to the
right to
3 Optimized Aisle
.
6. Go to Service Menu > Setpoints S146 Fan Control Sensor and set this to Remote. This parameter
only needs to be set for one unit. The other connected units in the group will auto-set themselves.
7. Adjust the rack temperature Setpoint at S147 to the desired value. This is typically set to 75, but
is customer preference.
8. Adjust S103 Temperature Setpoint to the desired value. This will must be set on a unit-to-unit
basis depending on the unit’s area of influence.
9. Monitor operation and adjust corresponding setpoints and control bands as needed.