Installation, Operation and Maintenance Manual
VCIOM-02377-EN Rev. 0
May 2022
21
Communication Interface
Section 8: Communication Interface
8.5
User Defined Data
The user defined data is stored in the EPI2 actuator and is available on the DeviceNet
network for Asset Management information.
Table 11.
Parameter 5: Class 100; Instance 1; Attribute 104
Table 12.
Parameter 6: Class 100; Instance 1; Attribute 105
Table 13.
Parameter 7: Class 100; Instance 1; Attribute 106
8.6
Configuration Data
The Configuration data is received from the base card via the internal data bus and is
reported to the DeviceNet network. The Configuration data can also be modified via the
DeviceNet network and the interface will send the new values to the logic board.
Table 14.
Parameter 8: Class 100; Instance 1; Attribute 112
Table 15.
Parameter 9: Class 100; Instance 1; Attribute 113
Table 16.
Parameter 10: Class 100; Instance 1; Attribute 114
Indication
Description
Direction Data type
Range
Default
E.U.
Actuator serial number Actuator serial number
Read only
Short string
12 bytes
-
-
Indication
Description
Direction Data type
Range
Default
E.U.
Actuator type
Actuator type
Read only
Short string
12 bytes
-
-
Indication
Description
Direction Data type
Range
Default
E.U.
Valve tag
Valve tag
Read only
Short string
12 bytes
-
-
Indication
Description
Direction Data type
Range
Default
E.U.
Close direction
The direction the actuator
drives the motor when it
receives a close command.
0 = Clockwise (CW)
1 = Counterclockwise
(CCW)
R/W
Integer
0-1
1
-
Indication
Description
Direction Data type
Range
Default
E.U.
Closing speed set
It defines the speed of the
motor when closing.
R/W
Integer
0-9
6
-
Indication
Description
Direction Data type
Range
Default
E.U.
Opening speed set
It defines the speed of the
motor when opening.
R/W
Integer
0-9
6
-