CAM216/16 IOM
Doc. Number: ECM-402-0116
January 2016, Rev. 1
3
Section 1: Introduction
Introduction
HART technology uses DD to achieve interoperability between actuators and control systems
or hosts from various manufacturers. For HART devices, in addition to providing parameter
definitions and information required by the control system to communicate with the HART
device, the DD may also include methods.
1.3
Disclaimer
All rights reserved. No part of this document shall be reproduced, stored in a retrieval system,
or transmitted by any means, electronic, mechanical, photocopying, recording, or otherwise
without the express written permission of Valve Automation. While every precaution has
been taken in the preparation of this document, the publisher and Valve Automation assume
no responsibility for technical or editorial errors, omissions made herein; nor for incidental
or consequential damages resulting from the performance or use of this document and the
information, apparatus, or methods of operations disclosed within this document.
WARNING:
Failure to follow instructions for proper electrical wiring, storage, setup, and maintenance
may cause serious injury, damage equipment, or void the warranty. Refer to Manual E796 for
instructions on storage, electrical hook-up and maintenance.
CAUTION:
Actuator failure or integral electronic controller configuration or setup beyond that is described
in this manual must be performed only by qualified Valve Automation personnel. Upgrades or
reconfiguration of existing actuators must be performed only by qualified Valve Automation
personnel. Repairs must be performed only by qualified Valve Automation personnel.
NOTE:
Advisory and information comments provided to assist personnel through additional details
and notable procedures
1.4
Actuator Description
Emerson Process Management electric actuators with HART option are microprocessor-based,
interoperable, process controllers, communicating with other valve actuators and types of
sensors and process control equipment. In addition to the primary function of controlling
the position of the valve, the Emerson Process Management electric actuator, using HART
communications protocol, gives easy access to information critical to process control. You can
gain information from the principal component of the process, the control valve itself, by using
a personal computer or operator’s console within the control room.
Using a compatible HART configuration device, you can obtain information about the health of
the actuator and valve. You can also obtain parameter access information about the actuator.
You can set input and output configuration parameters and calibrate the actuator. Using the
HART protocol, information from the actuator can be readily integrated into control systems
and process control strategies.