Introduction
1.5
Inputs & Outputs (I/O)
The flow computer comes with base I/O from both the CPU and the built-in multi-variable (MV)
sensor.
Base I/O consists of:
▪
Pressure (P) input from the MV sensor, differential pressure (DP) input from the MV sensor,
connections for temperature (T) input from a customer-supplied RTD/PRT
-or
–
a single
Static Pressure Sensor with RTD/PRT connections. Alternatively, you can purchase the flow
computer without an integral sensor.
▪
Either single digital output (DO) or four on-board I/O channels [two on-board I/O channels
you can individually configure as either digital input (DI), digital output (DO), or pulse input
(PI) and two on-board I/O channels you can individually configure as either analog input (AI)
or analog output (AO)].
Table 1-2. FB2100 I/O Configurations
Option
Configuration
FB2100 option 1
▪
MV Sensor (P, DP) or Static Pressure (SP) Sensor
▪
Connections for customer supplied 2, 3, or 4-wire RTD/PRT.
▪
1 DO channel
FB2100 option 2
▪
MV Sensor (P, DP) or Static Pressure (SP) Sensor
▪
Connections for customer supplied 2, 3, or 4-wire RTD/PRT.
▪
2 DI/DO/PI channels
▪
2 AI/AO channels
1.6
Power Options
You can power the flow computer using an external DC input, or an internal rechargeable battery
connected to a solar panel.
Important
Use only batteries supplied with the flow computer or sold by Emerson Remote Automation
Solutions as spare parts for this flow computer. If you substitute a battery you obtain elsewhere you
will void your certification unless it is the identical part from the same manufacturer as that
supplied with the flow computer from Emerson.
Table 1-3. Power Options
Option
Usage
External DC Power
Supply
10.5 Vdc to 30 Vdc external supply (Max power at 10 watts)
Lead Acid Battery Pack
▪
12 Vdc
▪
10.5 Ah
▪
Not suitable with ATEX or IECEx applications
▪
Can be optionally charged by a solar panel
Содержание FB2100
Страница 62: ...Emerson FB2100 Flow Computer Instruction Manual D301783X012 March 2019 58 Installation ...
Страница 76: ...Emerson FB2100 Flow Computer Instruction Manual D301783X012 March 2019 72 I O Configuration and Wiring ...
Страница 114: ...Emerson FB2100 Flow Computer Instruction Manual D301783X012 March 2019 Index 111 ...
Страница 115: ...Emerson FB2100 Flow Computer Instruction Manual D301783X012 March 2019 106 ATEX Non Sparking Zone 2 Certifications ...