2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature will be 
displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

HOW TO SEE THE SETPOINT 

 

1.

 

Push and immediately release the 

SET 

key: the display will show the Set 

point value; 

2.

 

Push and immediately release the 

SET 

key or wait for 5 seconds to  

display the probe value again. 

6.2

 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the 

SET 

key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “

°C” or “°F”

 LED starts blinking; 

3.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

4.

 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

6.4

 

HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows:  
1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Select the required parameter. Press the “

SET

” key to display its value 

3.

 

Use “

UP

” or “

DOWN

” to change its value. 

4.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5

 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.5.1  HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Released  the  keys,  then  push  again  the  Set+

n

  keys  for  more  than  7s.  The  Pr2  label  will  be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 

pushed till the Pr2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5.2  HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 
level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.6

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the 

UP

 +  

DOWN

 keys. 

2. 

 

The  “POF”  message  will  be  displayed  and  the  keyboard  will  be locked. At this point it will be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.7

 

TO UNLOCK THE KEYBOARD 

Keep  pressed  together  for  more  than  3s  the 

and 

n

  keys,  till  the 

“Pon” 

message  will  be 

displayed. 

6.8

 

THE CONTINUOUS CYCLE 

When  defrost  is  not  in  progress,  it  can  be  activated  by  holding  the  “

o

”  key  pressed  for  about  3 

seconds. The compressor operates to maintain the “

ccS

” set point for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

6.9

 

THE ON/OFF FUNCTION 

 

 

With “

onF = oFF

”, pushing the 

ON/OFF

 key, the instrument is switched off. The 

“OFF” 

message is displayed. In this configuration, the regulation is disabled.  
To switch the instrument on, push again the ON/OFF key. 

 

WARNING: Loads connected to the normally closed contacts of the relays are always supplied 
and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

REGULATION 
Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN is 

Set  Point  +  differential  (Hy).  Compressor  Cut  OUT  is  when  the  temperature  reaches  the  set 
point. 

LS  Minimum set point:

 (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 

US Maximum set point: 

(SET÷110°C/ SET÷230°F). Set the maximum value for set point. 

Ot    Thermostat  probe  calibration

:  (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Evaporator probe presence: n

= not present: the defrost stops by time; 

y=

 present: the defrost 

stops by temperature. 

OE Evaporator probe calibration:

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the evaporator probe. 

P3P  Third probe presence (P3): n

= not present:, the terminal operates as digital input.; 

y=

 present:, 

the terminal operates as third probe. 

O3 Third probe calibration  (P3):

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of the 

third probe. 

P4P Fourth probe presence

: (n = Not present; y = present). 

o4  Fourth probe calibration

: (-12.0

12.0°C) allows to adjust possible offset of the fourth probe. 

OdS Outputs activation delay at start up:

 (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC    Anti-short  cycle  delay

:  (0÷50  min)  minimum  interval  between  the  compressor  stop  and  the 

following restart. 

rtr  Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ): 

it allows 

to  set  the  regulation  according  to  the  percentage  of  the  first  and  second  probe,  as  for  the 
following formula (rtr(P1-P2)/100 + P2). 

CCt  Compressor  ON  time  during  continuous    cycle: 

(0.0÷24.0h;  res.  10min)  Allows  to  set  the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 
used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: 

(-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn  Compressor  ON  time  with  faulty  probe: 

(0÷255  min)  time  during  which  the  compressor  is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF  Temperature  measurement  unit: 

 

°C=

Celsius; 

°F

=Fahrenheit.  WARNING:  When  the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

Lod  Instrument  display

:  (P1;  P2,  P3,  P4,    SET,  dtr):  it  selects  which  probe  is  displayed  by  the 

instrument: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with 

this option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of visualization. 

rEd  X- REP display (

optional

)

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by X- 

REP: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with this 

option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of visualization. 

dLy  Display delay: 

(0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated of 

1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr 

it allows to set the visualization according to the percentage of the first 

and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

DEFROST 
dFP  Probe  selection  for  defrost  termination:  nP

  =  no  probe; 

P1

  =thermostat  probe; 

P2  = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

tdF   Defrost type

: EL = electrical heater; in = hot gas 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F)  (Enabled  only  when  EdF=Pb)  sets  the  temperature  measured  by  the  evaporator 
probe, which causes the end of defrost. 

IdF   Interval between defrost cycles

: (0÷120h) Determines the time interval between the beginning 

of two defrost cycles. 

MdF    (Maximum)  length  for  defrost

:  (0÷255min)  When 

P2P  =  n

,  (not  evaporator  probe:  timed 

defrost) it sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets the 

maximum length for defrost. 

dSd Start defrost delay

: ( 0÷99min) This is useful when different defrost start times are necessary to 

avoid overloading the plant.  

dFd  Temperature displayed during defrost

: (

rt

 = real temperature; 

it

 = temperature at defrost start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd  MAX  display  delay  after  defrost

:  (0÷255min).  Sets  the  maximum  time  between  the  end  of 

defrost and the restarting of the real room temperature display. 

Fdt  Drip time

: (0

120 min) time interval between reaching defrost termination temperature and the 

restoring  of  the  control’s  normal  operation.  This  time  allows  the  evaporator  to eliminate water 
drops that might have formed due to defrost. 

dPo  First defrost after start-up

: (y = immediately; n = after the IdF time) 

dAF  Defrost  delay  after  continuous  cycle

:  (0

23.5h)  time  interval  between  the  end  of  the  fast 

freezing cycle and the following defrost related to it. 

FANS 
FnC Fans operating mode

C-n

= runs with the compressor, OFF during defrost;  

o-n

 = continuous mode, OFF during defrost;  

C-Y

 = runs with the compressor, ON during defrost;  

o-Y

 = continuous mode, ON during defrost;  

Fnd Fans delay after defrost:

 (0÷255min) Interval between end of defrost and evaporator fans start.

 

Fct  Temperature differential avoiding short cycles of fans 

(0÷59°C; Fct=0 function disabled). If 

the  difference  of  temperature  between  the  evaporator  and  the  room  probes  is  more  than  the 
value of the Fct parameter, the fans are switched on.

 

FSt   Fans  stop  temperature

:  (-50÷50°C/122°F)  setting  of  temperature,  detected  by  evaporator 

probe, above which fans are always OFF. 

Fon Fan ON time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 
the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FoF Fan OFF time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 the 
fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FAP  Probe selection for fan management: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator 

probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

ALARMS 
ALC  Temperature alarms configuration:

 (Ab; rE) 

 

Ab=  absolute  temperature:  alarm  temperature  is  given  by  the  ALL  or  ALU  values.    rE  = 
temperature  alarms  are  referred  to  the  set  point.  Temperature  alarm  is  enabled  when  the 
temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU   MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

Содержание Dixell XR60CH

Страница 1: ...n be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again Time Temper C...

Страница 2: ... probe for regulation 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for instance when the room is filled w...

Страница 3: ...e The alarm stops just after the digital input is de activated 8 3 SERIOUS ALARM MODE i1F bAL When the digital input is activated the unit will wait for did delay before signalling the CA alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated 8 4 PRESSURE SWITCH i1F PAL If during the interval time set by did parameter the pressure switch h...

Страница 4: ...ator probe calibration 12 12 C 120 120 F 0 0 Pr2 P3P Third probe presence n not present Y pres n Pr2 O3 Third probe calibration 12 12 C 120 120 F 0 Pr2 P4P Fourth probe presence n not present Y pres n Pr2 O4 Fourth probe calibration 12 12 C 120 120 F 0 Pr2 OdS Outputs delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 50 min 1 Pr1 rtr P1 P2 percentage for regulation 0 100 100 P1 0 P2 10...

Отзывы: