background image

 

 

1592038000 XR60CH GB r1.0 05.05.2014 

XR60CH 

1/4 

Digital controller with defrost and fans management

 

XR60CH 

 

CONTENTS 

1.

 

GENERAL WARNING __________________________________________________________ 1

 

2.

 

GENERAL DESCRIPTION ______________________________________________________ 1

 

3.

 

CONTROLLING LOADS ________________________________________________________ 1

 

4.

 

FRONT PANEL COMMANDS ____________________________________________________ 1

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION _____________________________________ 1

 

6.

 

MAIN FUNCTIONS ____________________________________________________________ 2

 

7.

 

PARAMETERS _______________________________________________________________ 2

 

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N) ________________________________________ 3

 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS  _________________________________ 3

 

10.

 

X-REP OUTPUT – OPTIONAL ___________________________________________________ 3

 

11.

 

INSTALLATION AND MOUNTING ________________________________________________ 3

 

12.

 

ELECTRICAL CONNECTIONS___________________________________________________ 3

 

13.

 

HOW TO USE THE HOT KEY ___________________________________________________ 3

 

14.

 

ALARM SIGNALS _____________________________________________________________ 3

 

15.

 

TECHNICAL DATA ____________________________________________________________ 4

 

16.

 

CONNECTIONS ______________________________________________________________ 4

 

17.

 

DEFAULT SETTING VALUES ___________________________________________________ 4

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick 
reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 
cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to Dixell Srl 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XR60CH

, format 32 x 74 mm, is microprocessor based controller, suitable for applications on 

medium  or  low  temperature  ventilated  refrigerating  units.  It  has  three  relay  outputs  to  control 
compressor,  fan,  and  defrost,  which  can  be  either  electrical  or  reverse  cycle  (hot  gas).  It  is  also 
provided with three NTC or PTC probe inputs, the first one for temperature control, the second one, to 
be located onto the evaporator, to control the defrost termination temperature and to managed the fan, 
the  third  one,  optional,  to  connect  to  the  HOT  KEY  terminals  to  signal  the  condenser  temperature 
alarm or to display a temperature. The digital input can operate as fourth temperature probe. 
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  to a 
network  line 

ModBUS-RTU

  compatible  such  as  the 

dIXEL 

monitoring  units    of  X-WEB  family.  It 

allows to program the controller by means the HOT KEY programming  keyboard.  
The  instrument  is  fully  configurable  through  special  parameters  that  can  be  easily  programmed 
through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according to 
the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential  the  compressor  is 
started  and  then  turned  off  when  the 
temperature reaches the set point value 
again. 

Time

Temper.

Compr.

SET

ON

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters “

COn

” and “

COF

”. 

3.2

 

DEFROST 

Two defrost modes are available through the “

tdF

” parameter: defrost through electrical heater (

tdF = 

EL

) and hot gas  defrost (

tdF = in

). Other parameters are used to control the interval between defrost 

cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the evaporator’s 
probe (P2P).  
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt =0 the 
dripping time is disabled. 

3.3

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC = C_n:

  fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

FnC = o_n

  fans will run even if the compressor is off, and not run during defrost; 

After defrost, there is a timed fan delay allowing for drip time, set by means of the “

Fnd

” parameter. 

FnC = C_Y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC = o_Y

  fans will run continuously also during defrost 

 

An additional parameter “

FSt

” provides the setting of temperature, detected by the evaporator probe, 

above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in “FSt”. 

3.3.1  Forced activation of fans 

This  function  managed  by  the 

Fct

  parameter  is  designed  to  avoid  short  cycles  of  fans,  that  could 

happen when the controller is switched on or after a defrost, when the room air warms the evaporator. 

Functioning: 

if the difference of temperature between the evaporator and the room probes is more 

than the value of the Fct parameter, the fans are switched on. With Fct=0 the function is disabled. 

3.3.2  Cyclical activation of the fans with compressor off. 

When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF parameters 
the fans can carry out on and off cycles even if the compressor is switched off. When the compressor 
is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always off, when the 
compressor is off.  

4.

 

FRONT PANEL COMMANDS 

 

 

 

:  To  display  target  set  point;  in  programming mode it  selects a parameter  or confirm an 

operation. 

  (DEF) 

To start a manual defrost 

 

  (

UP)

:  To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the  parameter    

codes or increases the displayed value. 

 (

DOWN

) To see the min stored temperature; in programming mode it browses the parameter 

codes or decreases the displayed value. 

  

To switch the instrument off, if onF = oFF.  

 Not enabled. 

KEY COMBINATIONS: 

  

 



To lock & unlock the keyboard

.

 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

FUNCTION 

 

ON 

Compressor enabled 

 

Flashing 

Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

 

Flashing 

Drip time in progress 

 

ON 

Fans enabled 

 

Flashing 

Fans delay after defrost in progress. 

 

ON 

An alarm is occurring 

  ON 

Continuous cycle is running 

ECO

  ON 

Energy saving enabled 

°C/°F 

ON 

Measurement unit 

°C/°F 

Flashing 

Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt 
message will be displayed) 

Содержание Dixell XR60CH

Страница 1: ...n be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again Time Temper C...

Страница 2: ... probe for regulation 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for instance when the room is filled w...

Страница 3: ...e The alarm stops just after the digital input is de activated 8 3 SERIOUS ALARM MODE i1F bAL When the digital input is activated the unit will wait for did delay before signalling the CA alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated 8 4 PRESSURE SWITCH i1F PAL If during the interval time set by did parameter the pressure switch h...

Страница 4: ...ator probe calibration 12 12 C 120 120 F 0 0 Pr2 P3P Third probe presence n not present Y pres n Pr2 O3 Third probe calibration 12 12 C 120 120 F 0 Pr2 P4P Fourth probe presence n not present Y pres n Pr2 O4 Fourth probe calibration 12 12 C 120 120 F 0 Pr2 OdS Outputs delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 50 min 1 Pr1 rtr P1 P2 percentage for regulation 0 100 100 P1 0 P2 10...