1592038000 XR60CH GB r1.0 05.05.2014 

XR60CH 

4/4 

Message  

Cause 

Outputs 

“dA” 

Door open 

Compressor and fans restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL)  All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2”,

 “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check connections before 
replacing the probe. 
Temperature  alarms  “

HA

”,  “

LA

”  “

HA2

”  and  “

LA2

”  automatically  stop  as  soon  as  the  temperature 

returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

noA 

None alarm is recorded.

 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR60CH 

frontal 38x80 mm; depth 62mm; 

Mounting: XR60CH 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: XR60CH 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;  230Vac 

10%, 50/60Hz, 

110Vac 

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 4 NTC or PTC probes.

 

Digital input: 

 free voltage contact 

Relay outputs: compressor 

SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac or 20(8)A 250Vac

 

 

defrost: 

SPDT 8(3) A, 250Vac 

 

fan: 

SPST 8(3) A, 250Vac or SPST 5(2) A 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

16.

 

CONNECTIONS 

The X-REP

 

output

 

excludes

 the TTL output.. It’s present in the following codes:  

XR60CH- xx

2

xx, XR60CH –xx

3

xx; 

16.1

 

XR60CH – 8A OR 16A COMP. RELAY - 12VAC/DV OR 24 VAC/DV 

N.C.

Line

8(3)A250V

~

1 2 3 4 5

6

7

9 10 11 12

8(3)A

Max

16A

Comp

Def

Fan

Ev

ap

.

R

oo

m

8

Hot Key/IV probe/

TTL or X-REP output

 

 
NOTE: 

The compressor relay is 

8(3)A or 16(6)A according to the 
model. 

24Vac/dc supply

: connect to the 

terminals 7 and 8. 
 

16.2

 

XR60CH – 8A OR 16A COMP. RELAY - 120VAC OR 230 VAC 

N.C.

Line

8(3)A250V

~

1 2 3 4 5

6

6

9 10 11 12

8(3)A

Max

16A

Comp

Def

Fan

Ev

ap

.

R

oo

m

7

Hot Key/IV probe/

TTL or X-REP output

 

NOTE: 

The compressor relay is 

8(3)A or 16(6)A according to the 
model. 

120Vac supply

: connect to the 

terminals 6 and 7. 
 

 

16.3

 

XR60CH – 20A COMP. RELAY - 120VAC OR 230 VAC 

N.C.

Line

8(3)A250V

~

1 2 3 4 5

6

6

9 10 11 12

5(

1)

A

Max

20A

Comp

Def

Ev

ap

.

R

oo

m

7

Hot Key/IV probe

TTL or. X-REP output

Fan

8

20(8)A250V

~

 

 

120Vac supply

connect to the 
terminals 5 and 6. 
 

 

 
 

17.

 

DEFAULT SETTING VALUES  

Label 

Name 

Range 

°C/°F 

 

Set 

Set point 

LS÷US 

-5.0 

- - - 

Hy 

Differential 

0,1

25.5°C/ 1

 255°F 

2.0 

Pr1 

LS 

Minimum set point 

-50°C

SET/-58°F

SET 

-50.0 

Pr2 

US 

Maximum set point 

SET

110°C/ SET 

 230°F 

110 

Pr2 

Ot 

Thermostat probe calibration 

-12

12°C /-120

120°F 

0.0 

Pr1 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

Pr1 

OE 

Evaporator probe calibration 

-12

12°C /-120

120°F 

0.0 

Pr2 

P3P 

Third probe presence 

n=not present; Y=pres. 

Pr2 

O3 

Third probe calibration 

-12

12°C /-120

120°F 

Pr2 

P4P 

Fourth probe presence 

n=not present; Y=pres. 

Pr2 

O4 

Fourth probe calibration 

-12

12°C /-120

120°F 

Pr2 

OdS 

Outputs delay at start up 

0÷255 min 

Pr2 

AC 

Anti-short cycle delay 

 50 min 

Pr1 

rtr 

P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

-5 

Pr2 

COn 

Compressor ON time with faulty probe 

 255 min 

15 

Pr2 

COF 

Compressor OFF time with faulty probe  0 

 255 min 

30 

Pr2 

CF 

Temperature measurement unit 

°C 

 °F 

°C  

Pr2 

rES 

Resolution 

in=integer; dE= dec.point

 

dE  

Pr1 

Lod 

Probe displayed 

P1;P2 

P1 

Pr2 

rEd

X-REP display 

P1 - P2 - P3 - P4 - SEt - dtr 

P1 

Pr2 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

Pr2 

dtr 

P1-P2 percentage for disply 

 1 ÷ 99 

50 

Pr2 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL 

Pr1 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE 

Defrost termination temperature 

-50 

 50 °C 

Pr1 

IdF 

Interval between defrost cycles 

 120 ore 

Pr1 

MdF 

(Maximum) length for defrost 

 255 min 

30 

Pr1 

dSd 

Start defrost delay 

0÷99min 

Pr2 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

Fdt 

Draining time 

0÷120 min 

Pr2 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

Pr2 

Fnc 

Fan operating mode 

C-n, o-n, C-y, o-Y 

o-n 

Pr1 

Fnd 

Fan delay after defrost 

0÷255min 

10 

Pr1 

Fct 

Differential of temp. for forced fan active. 

0÷50°C 

10 

Pr2 

FSt 

Fan stop temperature 

-50÷50°C/-58÷122°F 

Pr1 

Fon 

Fan on time with compressor off 

0÷15 (min.) 

Pr2 

FoF 

Fan off time with compressor off 

0÷15 (min.) 

Pr2 

FAP 

Probe selection for fan management 

nP; P1; P2; P3; P4 

P2 

Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; Ab = absolute 

Ab 

Pr2 

ALU 

MAXIMUM temperature alarm 

Set

110.0°C; Set÷230°F 

110 

Pr1 

ALL 

Minimum temperature alarm 

-50.0°C

Set/ -58°F

Set 

-50.0 

Pr1 

AFH 

Differential for temperat. alarm recovery 

(0,1°C÷25,5°C) (1°F÷45°F) 

Pr2 

ALd 

Temperature alarm delay 

 255 min 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

 23h e 50’ 

1.3 

Pr2 

AP2 

Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2 

Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 

Pr2 

AU2 

Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 

Pr2 

AH2 

Differ. for condenser temp. alar. recovery  [0,1°C ÷ 25,5°C]  [1°F ÷ 45°F] 

Pr2 

Ad2 

Condenser temperature alarm delay  

 0 ÷ 254 (min.) , 255=nU 

15 

Pr2 

dA2 

Delay of cond. temper. alarm at start up 

0.0 ÷ 23h  50’ 

1,3 

Pr2 

bLL 

Compr. off for cond. low temp. alarm 

n(0) - Y(1) 

Pr2 

AC2 

Compr. off for cond. high temp. alarm 

n(0) - Y(1) 

Pr2 

i1P 

Digital input polarity 

oP=opening;CL=closing 

cL 

Pr1 

i1F 

Digital input configuration 

EAL, bAL, PAL, dor; dEF; Htr, AUS 

dor 

Pr1 

did 

Digital input alarm delay 

0÷255min 

15 

Pr1 

Nps 

Number of activation of pressure switch 

0 ÷15  

15 

Pr2 

odc 

Compress and fan status with open door 

no; Fan; CPr; F_C 

 

F-c 

Pr2 

rrd 

Regulation restart with door open alarm 

n – Y 

Pr2 

HES 

Differential for Energy Saving 

 (-30°C÷30°C) (-54°F÷54°F) 

Pr2 

PbC 

Kind of probe 

Ptc; ntc 

Pr2 

Adr 

Serrial address 

1÷247 

Pr2 

onF 

on/off key enabling 

nu, oFF; ES 

ntc 

Pr1 

dP1 

Room probe display 

-- 

nu 

Pr2 

dP2 

Evaporator probe display 

-- 

 -- 

Pr1 

dP3 

Third probe display 

-- 

 -- 

Pr1 

dP4 

Fourth probe display 

-- 

 -- 

Pr1 

rSE 

Valore set operativo 

actual set 

 -- 

Pr2 

rEL 

Software release 

-- 

 -- 

Pr2 

Ptb 

Map code 

-- 

 -- 

Pr2 

 

2

 Only for models XR60CH–xx

2

xx, XR60CH–xx

3

xx;  

 

 

Содержание Dixell XR60CH

Страница 1: ...n be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again Time Temper C...

Страница 2: ... probe for regulation 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for instance when the room is filled w...

Страница 3: ...e The alarm stops just after the digital input is de activated 8 3 SERIOUS ALARM MODE i1F bAL When the digital input is activated the unit will wait for did delay before signalling the CA alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated 8 4 PRESSURE SWITCH i1F PAL If during the interval time set by did parameter the pressure switch h...

Страница 4: ...ator probe calibration 12 12 C 120 120 F 0 0 Pr2 P3P Third probe presence n not present Y pres n Pr2 O3 Third probe calibration 12 12 C 120 120 F 0 Pr2 P4P Fourth probe presence n not present Y pres n Pr2 O4 Fourth probe calibration 12 12 C 120 120 F 0 Pr2 OdS Outputs delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 50 min 1 Pr1 rtr P1 P2 percentage for regulation 0 100 100 P1 0 P2 10...

Отзывы: