1592038000 XR60CH GB r1.0 05.05.2014 

XR60CH 

3/4 

ALL Minimum  temperature  alarm

:  (-50.0  ÷  SET°C;  -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH  Differential  for  temperature  alarm/  fan  recovery: 

(0,1÷25,5°C;  1÷45°F)  Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 
FSt temperature is reached  

ALd    Temperature  alarm  delay

:  (0÷255  min)  time  interval  between  the  detection  of  an  alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the LA2 

alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the HA2 

alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2  Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor  off  with  low  temperature  alarm  of  condenser

:

  n = no: 

compressor keeps on 

working

;  Y  =  yes, 

compressor  is  switched  off  till  the  alarm  is  present,  in  any  case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

;  Y  =  yes, 

compressor  is  switched  off  till  the  alarm  is  present,  in  any  case regulation 

restarts after AC time at minimum.

 

DIGITAL INPUT  
i1P  Digital input polarity: oP: 

the digital input is activated by opening the contact; 

CL: 

the digital 

input is activated by closing the contact.

 

i1F Digital input configuration: EAL 

= external alarm: “EA” message is displayed; 

bAL 

= serious 

alarm “CA” message is displayed. 

PAL 

= pressure switch alarm, “CA” message is displayed; 

dor

 

=  door  switch  function; 

dEF

  =  activation  of  a  defrost  cycle; 

AUS 

=not  enabled; 

Htr 

=  kind  of 

action inversion (cooling – heating); 

FAn = not set it; ES = 

Energy saving. 

did

:

 

(0

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay:

 delay between the detection 

of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F = PAL: time for pressure switch function: 

time interval to calculate the number of the 

pressure switch activation. 

nPS Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to restart 
normal regulation. 

odc  Compressor  and  fan  status  when  open  door:

   

no

  =  normal; 

Fan

  =  Fan  OFF; 

CPr 

Compressor OFF; 

F_C

 = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm;  

HES  Temperature increase during the Energy Saving cycle :

 (-30,0°C

30,0°C/-22÷86°F) it sets 

the increasing value of the set point during the Energy Saving cycle.  

OTHER 
Adr   Serial  address

  (1÷247):  Identifies  the  instrument  address  when  connected  to  a  ModBUS 

compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntc 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = not set it

dP1  Thermostat probe display 
dP2  Evaporator probe display 
dP3  Third probe display

optional

dP4  Fourth probe display

rSE  Real set point: 

(readable only), it shows the set point used during the energy saving cycle or 

during the continuous cycle. 

rEL  Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N) 

The free voltage digital input is programmable in different configurations by the “

i1F

” parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = 

normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is enabled, 

the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The alarm stops as 

soon as the external digital input is disabled again. With the door open, the high and low temperature 
alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As  soon  as  the  digital  input  is  activated  the  unit  will  wait  for  “

did

”  time  delay  before  signalling  the 

EAL

” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If  during  the  interval  time  set  by  “

did

”  parameter,  the  pressure  switch  has  reached  the  number  of 

activation  of    the  “

nPS

”  parameter,  the  “

CA

”  pressure  alarm  message  will  be  displayed.  The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 
OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

8.5

 

START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 
restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time 
is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+  HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The  TTL  serial  line,  available  through  the  HOT  KEY  connector,  allows  by  means  of  the  external 
TTL/RS485  converter, 

XJ485-CX

,  to  connect  the  instrument  to  a  monitoring  system 

ModBUS-RTU

 

compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY KEY connector. The X-
REP output 

EXCLUDES 

 the serial connection. 

 

To connect the X-REP to the instrument the 
following connectors must be used CAB-
51F(1m), CAB-52F(2m), CAB-55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR60CH

 shall be mounted on vertical panel, in a 29x71 

mm hole, and fixed using the special bracket supplied.  
The  temperature  range  allowed  for  correct  operation  is  0

60 °C. 

Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 
 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 
mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum current allowed on each relay, in case of heavier 
loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message appears 

followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, 

the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then on 

if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

Содержание Dixell XR60CH

Страница 1: ...n be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again Time Temper C...

Страница 2: ... probe for regulation 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for instance when the room is filled w...

Страница 3: ...e The alarm stops just after the digital input is de activated 8 3 SERIOUS ALARM MODE i1F bAL When the digital input is activated the unit will wait for did delay before signalling the CA alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated 8 4 PRESSURE SWITCH i1F PAL If during the interval time set by did parameter the pressure switch h...

Страница 4: ...ator probe calibration 12 12 C 120 120 F 0 0 Pr2 P3P Third probe presence n not present Y pres n Pr2 O3 Third probe calibration 12 12 C 120 120 F 0 Pr2 P4P Fourth probe presence n not present Y pres n Pr2 O4 Fourth probe calibration 12 12 C 120 120 F 0 Pr2 OdS Outputs delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 50 min 1 Pr1 rtr P1 P2 percentage for regulation 0 100 100 P1 0 P2 10...

Отзывы: