1592040000 XR20-30-60-70T EN v1.5 2021.06.22
XR20-30-60-70T
18/41
i2F
Digital input 2 configuration:
(nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; CC;
EMt)
•
nu
= not used
•
dor
= door switch function
•
dEF
= defrost activation
•
AUS
= auxiliary output
•
ES
= energy saving mode activation
•
EAL
= external warning alarm
•
bAL
= external lock alarm
•
PAL
= external pressure alarm
•
FAn
= evaporator fan control
•
HdF
= holiday defrost
•
onF
= ON/OFF status change
•
LiG
= light output control
•
CC
= continuous cycle mode
•
EMt
= Motion sensor X-MOD
•
MAP
= change parameter map (between C1 and C2)
d2d
Digital inputs 2 alarm delay (base time depends on par. ibt):
(0 to 255) delay between the
detection of an external event and the activation of the relative function.
nPS
Number of external pressure switch alarms before stopping the regulation:
(0 to 15) after
reaching nPS events in the digital input alarm delay (par. dxd), the regulation will be stopped and a
manual restart (ON/OFF, power OFF and power ON) will be required
odC
Compressor and fan status after door opening:
(no; FAn; CPr; F-C): no = normal;
FAn = Fans OFF; CPr = Compressor OFF; F-C = Compressor and fans OFF.
rrd
Regulation restart after door alarm:
(n; Y) n = no regulation if the door is open; Y = when the rrd
timer elapses, the regulation restarts even if a open door alarm is ON.
CLi
Light output activation from door input:
(n; Y) the activation of a digital input set as
ixF=dor
forces the light output ON.
LCi
Time with light output forced ON (0=function disabled):
(0 to 255 min) interval with light output
forced ON.
n01
Number of motion detections before activating light output (valid if ixF=EMt):
(0 to 10)
number of motion sensor detections before forcing the light output ON.
t01
Time with light output forced ON after motion detection:
(0 to 255 min) interval with light output
forced ON from motion sensor.
5.1.10 Energy saving configuration parameters - ES
ErA
Energy saving algorithm:
(nu; bAS)
nu
=disabled, the energy saving mode activation is by button,
real time clock or digital input;
bAS
=basic algorithm, the energy saving mode activation depends
on the the digital input.
HES
Energy saving mode temperature differential:
(-30.0 to 30.0°C; -54 to 54°F) sets the increasing
value of the set point during the Energy Saving cycle.
LdE
Energy saving controls the lights (lights OFF when energy saving is active):
(n; Y) lights off
when energy saving mode is active
StE
Period to switch from normal mode to energy saving mode:
(0.0 to 24h00min, res. 10 min) if
the door stay closed for
StE
time, the energy saving mode will be activated. NOTE: this will require
a door switch to work.
EtS
Period to switch from energy saving mode to normal mode:
(0.0 to 24h00min, res. 10 min)
maximum time for energy saving mode. NOTE: this will require a door switch to work.
dS
Door opening time to switch from EtS to StE:
(0 to 999 sec) the energy saving mode will be
immediately deactivated as soon as the door stays open more than the
dS
time. NOTE: this will
require a door switch to work.
nES
Number of motion detections before disabling energy saving mode (valid if ixF=EMt):
(0 to
255) number of motion sensor detections before disabling the energy saving mode.
5.1.11 Counters, read only values - Cnt
n1H
Number of activations for relay output oA1 (thousands of)