1592040000 XR20-30-60-70T EN v1.5 2021.06.22
XR20-30-60-70T
33/41
Energy
Saving
Normal
mode
Activate the ECO function from Virtual Keyboard screen.
Controller in ES mode for time
EtS
.
If the controller is in ES mode, it returns in Standard mode when the door
stays open more than time
dS
.
NOTE:
the cycling mode (ES - Normal mode - ES - etc.) works if
i1F=dor
,
EtS
and
StE
are different from
zero. If
EtS=0
or
StE=0,
the controller will not change the operating mode, and it will be possible to change
from the normal mode to the energy saving mode by using the ES button or by setting
i1F=ES
.
8.
PULL DOWN FUNCTION
The Pull Down is automatically activated:
•
After any defrost cycle
•
After power-on if
T>SET+CCS
•
When the regulation probe temperature
T
is:
o
T>SET+HY+oHt
value in normal mode
o
T>SET+HES+HYE+oHE
value in energy saving mode
In these cases, a different set-point value (
SET+CCS
) will be used. As soon as the room temperature
reaches the
SET+CCS
value, the compressor will stop and the normal regulation will restart.
NOTE:
•
Pull Down function is disabled when
CCS=0
or
CCt=0
.
•
The
CCt
parameter sets the maximum activation time for any pull down. When
CCt
expires, the Pull
Down will be immediately stopped and the standard SET-POINT will be restored
9.
DEFROST OPERATIONS
Any defrost operation can be controlled in the following way:
•
EdF=rtC
: by using an internal real-time clock (only for models equipped with RTC)
•
EdF=in
: timed defrost, in this case a new defrost will start as soon as the idF timer elapses
9.1 TIMED OR TEMPERATURE CONTROLLED MODE
Two defrost modes are available: timed or controlled by a temperature probe. A couple of parameters are
required to control intervals between defrost cycles (
idF
) and maximum duration (
MdF
). During a defrost
cycle it is possible to select some different visualizations by using the par.
dFd
. Available defrost types are:
•
tdF=EL
: with an electric heater
•
tdF=in
: by using hot gas cycle
10.
EVAPORATOR FAN
To enable the evaporator fan management, setting set an evaporator probe is required (par.
FAP
). Here are
the involved parameters:
•
FAP
: to select the control probe
•
FSt
: to select the deactivation set point
•
HYF
: differential
•
FnC
: to define the working mode:
o
C-n:
in parallel with compressor output and stopped during any defrost. When compressor is OFF,
they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
O-n:
always on, stopped during any defrost
o
C-Y:
in parallel with compressor output and always on during any defrost. When compressor is
OFF, they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
o-Y:
always on
•
Fnd:
activation delay after any defrost
10.1 EVAPORATOR FAN AND DIGITAL INPUT
When a digital input is configured as a door switch (
i1F or i2F=dor
) and this digital input is active, evaporator
fan and compressor status will depend on par.
odC
:
•
odC=no
: normal regulation
•
odC=FAn
: evaporator fan OFF
•
odC=CPr
: compressor OFF