![Emerson Dixell XR20T Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/emerson/dixell-xr20t/dixell-xr20t_operating-instructions-manual_102156037.webp)
1592040000 XR20-30-60-70T EN v1.5 2021.06.22
XR20-30-60-70T
37/41
Always check the connections (probe
– device terminals) before replacing the probe. Temperature alarms
HA
,
LA
,
H2
and
L2
are automatically reset as soon as the temperature is within the normal working range. It is
possible to reset the “
EE
” alarm by pressing any button.
The alarms
EA
,
CA
and
dA
are automatically reset as soon as the relative digital input is disabled.
The internal buzzer can be muted by touching any area of the display and only if parameter
tbA=Y
.
15.
SERIAL COMMUNICATION
The device supports different baudrates (par.
bAU
) and parity control (par.
PAr
).
Please check the serial network to adapt them according to the other devices. The
XJ485CX
serial interface is required to convert the TTL output into an RS485 signal.
16.
INSTALLATION AND MOUNTING
Instrument
XR-T
shall be mounted on vertical panel, in a 29x71 mm hole,
and fixed using the special bracket supplied. The temperature range
allowed for correct operation is 0 to 60°C. Avoid places subject to strong
vibrations, corrosive gases, excessive dirt or humidity. The same
recommendations apply to probes. Let air circulate through the cooling
holes.
17.
WIRING DIAGRAMS
17.1 XR70T
Power Supply:
110VAC, 230VAC or
100-240VAC, 50-60Hz
oA1:
always set as main compressor
output (CP1)
17.2 XR60T
Power Supply:
110VAC, 230VAC or
100-240VAC, 50-60Hz
oA1:
always set as main compressor
output (CP1)
Содержание Dixell XR20T
Страница 1: ...Full Touch XR20T XR30T XR60T XR70T V 1 5 ...
Страница 2: ......